TABLE 4: COOLING CAPACITIES - BP 240 20 TON (CONTINUED)
AIR ON
EVAPORATOR
COIL
TEMPERATURE OF AIR ON OUTDOOR COIL
125ºF
TOTAL
CAP.
1
MBH
POWER
INPUT
2
KW
SENSIBLE CAPACITY
1
, MBH
ENTERING DRY BULB
CFM
WB
ºF
86 83 80 77 74 71 68
6000
72 208.0 23.1 140.3 123.1 106.0 88.9 71.8 #N/A #N/A
67 185.8 22.9 171.6 158.4 141.3 124.2 107.1 90.0 72.9
62 169.1 22.6 171.6 169.1 157.0 139.9 122.8 105.7 88.6
57 171.6 22.5 171.6 171.6 155.4 138.3 121.2 104.1 86.9
7000
72 214.4 23.3 155.6 135.4 115.2 94.9 74.7 #N/A #N/A
67 191.4 23.1 176.8 173.6 153.4 133.2 113.0 92.8 72.6
62 174.2 22.8 176.8 176.8 170.5 150.3 130.1 109.9 89.7
57 176.8 22.6 176.8 176.8 168.7 148.5 128.3 108.1 87.8
8000
72 220.7 23.5 170.9 147.6 124.3 100.9 77.6 #N/A #N/A
67 197.1 23.3 182.1 179.4 165.6 142.2 118.9 95.6 72.3
62 179.4 23.0 182.1 182.1 179.4 160.7 137.4 114.0 90.7
57 182.1 22.8 182.1 182.1 179.4 158.7 135.4 112.1 88.8
8350
72 221.3 23.6 175.6 150.9 126.3 101.7 77.1 #N/A #N/A
67 197.6 23.4 182.5 182.5 168.3 143.7 119.1 94.4 69.8
62 179.9 23.1 182.5 182.5 179.9 157.5 132.9 108.3 83.6
57 182.5 22.9 182.5 182.5 182.5 157.9 133.3 108.6 84.0
8700
72 221.9 23.8 180.2 154.3 128.4 102.4 76.5 #N/A #N/A
67 198.1 23.6 183.0 177.0 171.1 145.2 119.2 93.3 67.4
62 180.3 23.2 183.0 183.0 180.3 154.4 128.4 102.5 76.6
57 183.0 23.1 183.0 183.0 183.0 157.1 131.1 105.2 79.3
1 The capacities are gross ratings. For Net capacity,
deduct the supply air blower motor heat, MBH =
3.415 X Kw. Refer to the appropriate blower perfor-
mance table for the Kw of the supply air blower
motor.
2 These ratings include condenser fan motor and com-
pressor motor power but not the supply air blower
motor power.