York Sunline 2000 - Electronic Thermostat Field Wiring; Field Wiring 24 Volt Thermostat

York Sunline 2000
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
036-21490-002-A-0204
Unitary Products Group 21
NOTE: This unit does NOT REQUIRE a heat pump thermo-
stat. It is designed to work with a standard two-stage
cool, two-stage heat thermostat; however, the ther-
mostat must provide a “G” signal when there is a call
for “W1”.
FIGURE 3 - ELECTRONIC THERMOSTAT FIELD WIRING
W 2
R C
R H
Y 1
Y 2
W 1
G
C
X 1
X 3
X 4
A 1
A 2
T
T
T H E R M O S T A T *
T E R M I N A L S
U N I T T E R M I N A L S
S T R I P T B 1
*
E l e c t r o n i c p r o g r a m m a b l e T h e r m o s t a t 2 E T 0 7 7 0 0 1 0 0 2 4 ( i n c l u d e s s u b b a s e ) .
T e r m i n a l s A 1 a n d A 2 p r o v i d e a r e l a y o u t p u t t o c l o s e t h e o u t d o o r
e c o n o m i z e r d a m p e r s w h e n t h e t h e r m o s t a t s w i t c h e s t o t h e s e t - b a c k p o s i t i o n .
2 4 V o l t
T r a n s f o r m e r
T O R E M O T E S E N S O R
2 E T 0 4 7 0 1 3 2 4 I F U S E D
O C C
W 1
W 2
Y 1
G
Y 2
X
R
S D
C
R E M O T E
M I N P O S
FIGURE 4 - FIELD WIRING 24 VOLT THERMOSTAT
O C C
W 1
W 2
Y 1
G
Y 2
X
R
S D
C
R E M O T E
M I N P O S
W 1
W 2
Y 1
G
Y 2
C
U N I T C O N T R O L
B O A R D
T - S T A T
R H
R C
The thermostat must provide a “G” signal
when there is a call for “W1.”The unit control
board will energize the indoor blower when
the compressors are energized; however, if
the thermostat calls for “W2” during the anti-
short-cycle delay, the electric heat (when
installed) will be energized immediately
upon the call for “W2.
The thermostat must provide a “G” signal
when there is a call for “W1.”The unit control
board will energize the indoor blower when
the compressors are energized; however, if
the thermostat calls for “W2” during the anti-
short-cycle delay, the electric heat (when
installed) will be energized immediately
upon the call for “W2.”