400034-YTG-B-0708
6 Johnson Controls Unitary Products
— = Not applicable.
13 SEER AC WITH AHP / SHP / F*FP
TCGD12S21S2(H) AHP18 17 –
450 12.0 8.9 13.00 11.00
TCGD18S21S2(H)
AHP18 17 –
650 18.0 12.6 13.00 11.00
AHP24 17 –
650 18.0 12.6 13.00 11.00
F4FP024 18 –
600 18.0 12.6 1300 11.00
TCGD24S21S2(H)
AHP30 17 –
795 24.0 17.3 13.00 11.00
F4FP036 21.5 –
860 24.0 17.3 13.00 11.00
TCGD30S21S2(H)
AHP30 17 –
1015 29.0 21.2 13.00 11.00
AHP36 21 –
1015 29.0 21.2 13.00 11.00
F4FP040 21.5 –
1000 29.0 21.2 13.00 11.00
TCGD36S21S2(H)
AHP36 21 –
1235 35.0 24.4 13.00 11.00
F5FP048 24 –
1235 35.0 24.4 13.00 11.00
TCGD42S21S2(H)
AHP42 21 –
1485 42.0 29.4 13.00 11.00
F5FP048 24 –
1455 42.0 29.4 13.00 11.00
TCGD48S21S2(H)
AHP/SHP60 24 –
1600 46.0 33.0 13.00 11.00
F5FP048 24 –
1690 46.0 33.0 13.00 11.00
F5FP060 24 –
1680 46.0 33.0 13.00 11.00
Rated in accordance with DOE test procedures (Federal Register 12-27-79 and 3-18-88) and ARI Standards 210.
Cooling MBH based on 80°F entering air temperature, 50% RH, and rated air flow.
EER (Energy Efficiency Ratio) is the total cooling output in BTU’s at 95°F outdoor ambient divided by the total electric power in watt-hours at those conditions.
SEER (Seasonal Energy Efficiency Ratio) is the total cooling output in BTU’s during a normal annual usage period for cooling divided by the total electric power
input in watt-hours during the same period.
1. MC coils available with a factory installed horizontal drain pan. See price pages for specific model number.
COOLING CAPACITY - With Air Handler Coils (Continued)
UNIT
MODEL
AIR HANDLER
COIL
MODEL
1
COOLING
MODEL W
RATED
CFM
NET MBH
SEER EER
TOTAL SENS.
CONDENSER ONLY DATA
Model
Suct. T/P @ Compr.
Air Temp on Condenser
75° F 95° F 115° F
Temp. PSIG MBH KW MBH KW MBH KW
TCGD12S21S2(H)
SH 11 / SC 13 @
95 OD Temp
40 68.6 11.81 0.73 8.15 0.85 5.29 1.01
45 76.1 12.65 0.73 10.15 0.86 7.21 1.02
50 84.1 13.55 0.74 12.29 0.87 9.26 1.04
TCGD18S21S2(H)
SH 11 / SC 10 @
95 OD Temp
40 68.6 17.53 1.07 15.03 1.29 11.98 1.57
45 76.1 18.63 1.07 17.25 1.30 14.07 1.59
50 84.1 19.80 1.08 19.61 1.31 16.30 1.61
TCGD24S21S2(H)
SH 10 / SC 12 @
95 OD Temp
40 68.6 22.88 1.42 19.07 1.70 13.99 2.02
45 76.1 24.93 1.44 22.25 1.72 17.25 2.07
50 84.1 27.12 1.47 25.63 1.75 20.72 2.12
TCGD30S21S2(H)
SH 12 / SC 10 @
95 OD Temp
40 68.6 28.77 1.75 23.85 2.01 17.06 2.21
45 76.1 30.28 1.80 26.56 2.07 19.76 2.31
50 84.1 31.89 1.86 29.45 2.13 22.64 2.40
TCGD36S21S2(H)
SH 10 / SC 11 @
95 OD Temp
40 68.6 31.46 2.16 18.41 2.37 13.42 2.78
45 76.1 36.54 2.20 25.84 2.47 18.88 2.85
50 84.1 41.95 2.24 33.77 2.58 24.71 2.91
TCGD42S21S2(H)
SH 10 / SC 9 @ 95
OD Temp
40 68.6 40.44 2.46 28.86 2.83 21.78 3.21
45 76.1 45.28 2.52 36.10 2.91 27.55 3.30
50 84.1 50.44 2.59 43.82 3.00 33.70 3.41
TCGD48S21S2(H)
SH 10 / SC 12 @
95 OD Temp
40 68.6 42.04 2.70 26.14 3.03 21.19 3.49
45 76.1 46.86 2.77 35.10 3.16 27.59 3.60
50 84.1 52.00 2.85 44.65 3.30 34.43 3.73
TCGD60S21S2
SH 10 / SC 9 @ 95
OD Temp
40 68.6 52.76 3.40 46.38 4.04 36.26 5.08
45 76.1 59.98 3.41 53.35 4.14 42.46 5.15
50 84.1 67.69 3.41 60.79 4.25 49.07 5.22