EasyManua.ls Logo

York TCGD18 THRU 60 - R-410 A Charge and Orifice Data; Indoor Coil Matching and Refrigerant Charge; R-410 A Data Table Footnotes

York TCGD18 THRU 60
18 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
359315-YTG-B-0408
Johnson Controls Unitary Products 3
Additional R-410A Charge / Orifice Size for Various Matched Systems
Outdoor Unit
TCGD18
S41S1(H)
TCGD24
S41S1(H)
TCGD30
S41S1(H)
TCGD36
S41S1(H)
TCGD42
S41S1(H)
TCGD48
S41S1(H)
TCGD60
S41S1
Required Orifice or TXV
1,2
0.048 / 902 0.055 / 902 0.061 / 907 0.065 / 903 0.075 / 903 0.073 / 904 0.087 / 905
Factory Charge, lbs-oz 3 - 3 3 - 13 3 - 14 4 - 9 4 - 5 4 - 9 5 - 6
Indoor Coil
3,4
Additional Charge, Oz
FC/MC/PC/UC18A3X
48 + 0 ––––––
902 + 0 ––––––
FC/MC/PC/UC18B3X
48 + 0 ––––––
902 + 0 ––––––
FC/MC/PC32A3X
55 + 4 61 + 0 ––––
902 + 4 907 + 0 ––––
FC/MC/PC35B3X
55 + 4 61 + 0 ––––
902 + 4 907 + 0 ––––
FC/MC/PC35C3X
55 + 4 61 + 0 ––––
902 + 4 907 + 0 ––––
FC/MC/PC/UC36A3X
55 + 0 –––––
902 + 0 –––––
FC/MC/PC/UC36B3X
55 + 0 –––––
902 + 0 –––––
FC/MC/PC/UC36C3X
55 + 0 –––––
902 + 0 –––––
FC/MC/PC37A3X
55 + 4 61 + 2 65 + 0
902 + 4 907 + 2 903 + 0
FC/MC/PC43B3X
55 + 4 61 + 2 65 + 0 75 + 0
902 + 4 907 + 2 903 + 0 903 + 0
FC/MC/PC43C3X
55 + 4 61 + 2 65 + 0 75 + 0
902 + 4 907 + 2 903 + 0 903 + 0
FC/MC/PC/UC48C3X
65 + 8 75 + 2 73 + 4
903 + 8 903 + 2 904 + 4
FC/MC/PC/UC48D3X
65 + 8 75 + 2 73 + 4
903 + 8 903 + 2 904 + 4
FC/MC/PC/UC60D3X
–––––73 + 0 87 + 0
–––––904 + 0 905 + 0
FC/MC62D3X
––––––87 + 4
––––––905 + 4
HC18A3X
48 + 0 ––––––
902 + 0 ––––––
HC30A3X
55 + 0 –––––
902 + 0 –––––
HC36B3X
55 + 4 61 + 0 ––––
902 + 4 907 + 0 ––––
HC42C3X
55 + 4 61 + 2 65 + 0 75 + 0
902 + 4 907 + 2 903 + 0 903 + 0
HC60D3X
––––––87 + 0
––––––905 + 0
AHP18B3X
48 + 0 ––––––
902 + 0 ––––––
AHP30B3X
55 + 4 61 + 0 ––––
902 + 4 907 + 0 ––––
AHP36C3X
61 + 2 65 + 0
907 + 2 903 + 0
AHP42C3X
65 + 0 75 + 0
903 + 0 903 + 0