5591306-YTG-F-0220
Johnson Controls Ducted Systems 3
‡ Adapter fitting must be field installed for the required 1-1/8” line set.
All dimensions are in inches and are subject to change without notice.
Overall height is from bottom of base pan to top of fan guard.
Overall length and width include screw heads.
PHYSICAL AND ELECTRICAL DATA
MODEL
THE30
B31S
THE36
B32S
THE42
B33S
THE48
B31S
THE60
B31S
THE30
B41S
THE36
B42S
THE42
B43S
THE48
B41S
THE60
B41S
Unit Supply Voltage 208-230V, 3, 60Hz 460V, 3, 60Hz
Normal Voltage Range
1
1. Rated in accordance with AHRI Standard 110-2012, utilization range “A”.
187 to 252 432 to 504
Minimum Circuit Ampacity 12.5 15.8 19.7 18.5 21.3 6.0 8.8 9.1 8.7 10.4
Max. Overcurrent Device Amps
2
2. Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.
20 25 30 30 35 15 15 15 15 15
Min. Overcurrent Device Amps
3
3. Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.
15 20 20 20 25 15 15 15 15 15
Compressor
Type Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll
Rated Load Amps 9.9 10.4 13.5 15.3 17.8 4.7 5.8 6.0 6.9 8.6
Locked Rotor Amps 58.0 73.0 88.0 83.1 110.0 38.0 38.0 44.0 41.0 52.0
Crankcase Heater No No No No No No No No No No
Factory External Discharge Muffler Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes
Fan Diameter Inches 24 26 26 26 26 24 26 26 26 26
Fan Motor
Type PSC ECM ECM PSC PSC PSC ECM ECM PSC PSC
Rated HP 1/4 1/3 1/3 1/4 1/4 1/4 1/3 1/3 1/4 1/4
Rated Load Amps 1.30 2.8 2.8 1.30 1.30 0.65 1.6 1.6 0.60 0.60
Nominal RPM 850 834 834 850 850 850 834 834 850 850
Nominal CFM 2995 3715 4000 4100 4100 2995 4000 4000 4100 4100
Coil
Face Area Sq. Ft. 23.82 26.40 26.40 26.40 28.80 23.82 26.40 26.40 26.40 28.80
Rows Deep 1 1 1 2 2 1 1122
Fins / Inch 22 22 22 18 18 22 22 22 18 18
Liquid Line Set OD (Field Installed) 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8
Vapor Line Set OD (Field Installed)
4
4. For applications with non-standard vapor line sizes, see the “Applications & Accessories” section of this Technical Guide.
3/4 3/4 7/8 7/8
1-1/8
‡
3/4 3/4 7/8 7/8
1-1/8
‡
Unit Charge (Lbs. - Oz.)
5
5. The Unit Charge is correct for the outdoor unit, smallest matched indoor unit, and 15 feet of refrigerant tubing. For tubing lengths other than 15 feet, add or subtract
the amount of refrigerant, using the difference in actual lineset length (not the equivalent length) multiplied by the per foot value.
7 - 15 9 - 1 10 - 5 15 - 4 14 - 10 7 - 15 9 - 1 10 - 5 15 - 4 14 - 10
Charge Per Foot, Oz. 0.62 0.62 0.67 0.67 0.75 0.62 0.62 0.67 0.67 0.75
Operating Weight Lbs. 181 235 235 240 261 181 235 235 240 261
&
%
$
$
DIMENSIONS
Unit
Model
Dimensions
(Inches)
Refrigerant Connection
Service Valve Size
A B C Liquid Vapor
THE30B(3,4)1S 39-1/2 35-1/4 31-3/4
3/8
3/4
THE36B(3,4)2S 39-1/2 38 34-1/4
THE42B(3,4)3S 39-1/2 38 34-1/4
7/8
THE48B(3,4)1S 39-1/2 38 34-1/4
THE60B(3,4)1S 42-3/4 38 34-1/4
7/8
‡