CP equals MBH output divided by (total KW input x 3.412).
HSPF (Heating Seasonal Performance Factor) is the total heating output during a normal annual usage period for heating divided by
the total electric power input during the same period.
— = Not Applicable.
HEATING PERFORMANCE - Upflow, Downflow, and Horizontal Furnaces and Coils
UNIT
MODEL*
COIL
1
MODEL
ARI HEATING
2
47°F17°FHSPF
MBH COP KW MBH COP KW STD
THGD18S41S1
FC/MC/PC/UC1 17.0 3.32 1.50 12.7 3.00 1.24 7.70
FC/MC/PC/UC2 17.0 3.44 1.45 10.4 2.60 1.17 7.70
HC18 17.0 3.32 1.50 12.7 3.00 1.24 7.70
HC30 17.0 3.38 1.47 10.4 2.60 1.17 7.70
HD24 16.6 3.16 1.54 12.8 3.00 1.25 7.70
THGD24S41S1
FC/MC/PC24 23.2 3.40 2.00 12.6 2.24 1.65 7.70
FC/MC/PC30 23.2 3.40 2.00 12.6 2.24 1.65 7.70
FC/MC/PC32 23.2 3.40 2.00 12.6 2.24 1.65 7.70
FC/MC/PC35 23.2 3.40 2.00 12.6 2.24 1.65 7.70
HC30 23.0 3.40 1.98 12.6 2.24 1.65 7.70
HC36 23.2 3.40 2.00 12.6 2.24 1.65 7.70
HD36 23.2 3.40 2.00 12.6 2.24 1.65 7.70
THGD30S41S1
FC/MC/PC32 28.0 3.34 2.46 16.4 2.28 2.11 7.70
FC/MC/PC35 28.0 3.34 2.46 16.4 2.30 2.09 7.70
FC/MC/PC37 28.2 3.40 2.43 16.6 2.32 2.10 7.70
FC/MC/PC43 28.2 3.40 2.43 16.6 2.32 2.10 7.70
HC36 28.2 3.34 2.47 16.4 2.28 2.11 7.70
HC42 28.2 3.40 2.43 16.6 2.32 2.10 7.70
HD48 28.2 3.60 2.30 16.6 2.32 2.10 7.70
THGD36S41S1
FC/MC/PC37 35.0 3.40 3.02 21.2 2.36 2.63 8.00
FC/MC/PC43 35.0 3.42 3.00 21.2 2.36 2.63 8.00
FC/MC/PC48 35.0 3.42 3.00 21.4 2.36 2.66 8.00
HC42 35.0 3.42 3.00 21.2 2.36 2.63 8.00
HD48 35.0 3.40 3.02 20.0 2.16 2.71 8.00
THGD42S41S1
FC/MC/PC48 41.0 3.48 3.45 28.0 2.46 3.34 8.00
FC/MC/PC60 41.0 3.66 3.28 27.8 2.56 3.18 8.00
HC42 41.0 3.46 3.47 27.8 2.48 3.29 8.00
HC60 41.0 3.66 3.28 27.8 2.56 3.18 8.00
HD60 41.0 3.14 3.83 27.6 2.26 3.58 8.00
THGD48S41S1
FC/MC/PC48 50.5 3.32 4.46 30.8 2.24 4.03 8.00
FC/MC/PC60 51.0 3.50 4.27 30.6 2.34 3.83 8.00
HC60 51.0 3.50 4.27 30.6 2.34 3.83 8.00
HD60 50.0 2.98 4.92 30.6 2.06 4.35 8.00
MC62 50.5 3.38 4.38 30.6 2.28 3.93 8.00
THGD60S41S1 MC62 56.5 3.48 4.76 35.4 2.42 4.29 8.00
1. Rated CFM same as for cooling.
2. Heating MBH based on ARI standards of 70° DB entering indoor air, 72% RH outdoor air with 25 feet of interconnecting piping and
no supplemental electric heat operation.