TECHNICAL GUIDE
SPLIT-SYSTEM
HEAT PUMPS
13 SEER – R-410A
MODELS:
THGD18 THRU 60
(1.5 THRU 5 NOMINAL TONS, 1 PHASE)
Due to continuous product improvement, specifications
are subject to change without notice.
V
isit us on the web at www.york.com
A
dditional rating information can be found at
w
ww.ahridirectory.org
LISTED
ISO 9001
Certified Quality
Management System
397763-YTG-B-0508
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
DESCRIPTION
The heat pump condensing unit is the outdoor part of a versa-
tile system of heating and air conditioning. It is designed to be
custom-matched with one of UPG’s complete line of evapora-
tor sections, with each serving a specific function. Matching
Air Handlers are available for upflow, downflow, or horizontal
applications to provide a complete system. Electric Heaters
are available, if required. Add-on coils are available for use
with upflow, downflow, or horizontal furnaces and air han-
dlers.
WARRANTY
Single Phase Units:
5-year limited parts warranty.
5-year limited compressor warranty.
FEATURES
QUALITY CONDENSER COILS - The coil is constructed
of copper tubing and enhanced aluminum fins for
increased efficiency and corrosion protection.
PROTECTED COMPRESSOR - The compressor is inter-
nally protected against high pressure, temperature, and
externally by a factory installed high pressure switch. This
is accomplished by the simultaneous operation of high
pressure relief valve and a temperature sensor which pro-
tects the compressor if undesirable operating conditions
occur. A liquid line filter-drier further protects the compres-
sor.
DURABLE FINISH - The cabinet is made of pre-painted
steel. The pre-treated galvanized steel provides a better
paint to steel bond, which resists corrosion and rust creep.
Special primer formulas and matted-textured finish insure
less fading when exposed to sunlight.
LOWER INSTALLED COST - Installation time and costs
are reduced by easy power and control wiring connec-
tions. Available in sweat connect models only. The unit
contains enough refrigerant for matching indoor coils and
15 feet of interconnecting piping. The small base dimen-
sion means less space is required on the ground or roof.
TOP DISCHARGE - The warm air from the top mounted
fan is blown up away from the structure and any landscap-
ing. This allows compact location on multi-unit applica-
tions.
LOW OPERATING SOUND LEVEL - The upward air flow
carries the normal operating noise away from the living
area. The rigid top panel effectively isolates any motor
sound. Isolator mounted compressor and the rippled fins
of the condenser coil muffle the normal fan motor and
compressor operating sounds.
LOW MAINTENANCE - Long life permanently lubricated
motor-bearings need no annual servicing.
EASY SERVICE ACCESS - Fully exposed refrigerant con-
nections, and a single panel covering the electrical con-
trols make for easy servicing of the unit.
SECURED SERVICE VALVES - Secured re-usable ser-
vice valves are provided on both the liquid and vapor
sweat connections for ease of evacuating and charging.
U.L. and C.U.L. listed - approved for outdoor application.
Certified in accordance with the Unitary Small Equipment cer-
tification program, which is based on ARI Standard 210/240.
Question and Answer IconNeed help?

Do you have a question about the York THGD18 THRU 60 and is the answer not in the manual?

Summary

Technical Guide Overview

Split-System Heat Pumps

Details for split-system heat pumps, 13 SEER, R-410A, and model information.

Physical and Electrical Specifications

R-410 A Charge and Orifice Sizing

Cooling Capacity with Air Handler Coils

Cooling Capacity with Furnace Systems

Cooling Capacity with Variable Speed Furnaces

Heating Performance with Air Handlers

Heating Performance with Furnace Systems

Heating Capacity with Variable Speed Furnaces

System Accessories

Typical Installation Guidelines

Typical Field Wiring Connections

Cooling Performance Data Tables

Heating Performance Data Tables

Overview

The YORK Split-System Heat Pump is an outdoor condensing unit designed for heating and air conditioning, suitable for custom-matching with various UPG evaporator sections. It is compatible with air handlers for upflow, downflow, or horizontal applications, and can be paired with electric heaters or add-on coils for furnaces.

Technical Specifications:

The models covered are THGD18 through THGD60, ranging from 1.5 to 5 nominal tons, 1 phase. All units operate on 208-230V, 1 phase, 60Hz power, with a normal voltage range of 187 to 252V.

  • Minimum Circuit Ampacity: Ranges from 9.6A (THGD18) to 37.4A (THGD60).
  • Max. Overcurrent Device Amps: Ranges from 15A (THGD18) to 60A (THGD60).
  • Min. Overcurrent Device Amps: Ranges from 15A (THGD18) to 40A (THGD60).
  • Compressor Type: THGD18-36 models use Reciprocating compressors, while THGD42-60 models use Scroll compressors.
  • Compressor Amps (Rated Load): Ranges from 7.12A (THGD18) to 28.79A (THGD60).
  • Compressor Amps (Locked Rotor): Ranges from 47.0A (THGD18) to 150.0A (THGD48/60).
  • Crankcase Heater: Included on THGD18-36 models.
  • Fan Motor Amps (Rated Load): Ranges from 0.70A (THGD18) to 1.5A (THGD36-60).
  • Fan Diameter: 24 inches for all models.
  • Fan Motor Rated HP: 1/10 HP (THGD18), 1/8 HP (THGD24-30), 1/4 HP (THGD36-60).
  • Nominal RPM: Ranges from 825 (THGD18) to 1075 (THGD24-30) to 850 (THGD36-60).
  • Nominal CFM: Ranges from 2200 (THGD18) to 3800 (THGD36) to 3000 (THGD48/60).
  • Coil Rows Deep: 1 (THGD18-42), 2 (THGD48-60).
  • Fin/Inches: 22 (THGD18-42), 18 (THGD48-60).
  • Liquid Line Set OD (Field Installed): 3/8 inch for all models.
  • Vapor Line Set OD (Field Installed): 3/4 inch (THGD18-36), 7/8 inch (THGD42-60).
  • Unit Charge (Lbs. - Oz.): Ranges from 6-5 (THGD18) to 13-6 (THGD60).
  • Charge Per Foot (Oz.): 0.62 oz/ft (THGD18-36), 0.67 oz/ft (THGD42-60).
  • Operating Weight: Ranges from 172 lbs (THGD18) to 280 lbs (THGD60).

Usage Features:

  • Quality Condenser Coils: Constructed with copper tubing and enhanced aluminum fins for improved efficiency and corrosion resistance.
  • Protected Compressor: Features internal protection against high pressure and temperature, and external protection via a factory-installed high-pressure switch. A high-pressure relief valve and temperature sensor further safeguard the compressor. A liquid line filter-ddrier is also included.
  • Durable Finish: The cabinet is made of pre-painted steel with a pre-treated galvanized base for superior paint adhesion, corrosion, and rust resistance. Special primer formulas and a matted-textured finish minimize fading from sunlight exposure.
  • Lower Installed Cost: Simplified power and control wiring connections reduce installation time and costs. Units are pre-charged with enough refrigerant for matching indoor coils and 15 feet of interconnecting piping. The compact base dimensions allow for flexible ground or roof placement.
  • Top Discharge: The top-mounted fan blows warm air upwards, away from the structure and landscaping, making it suitable for multi-unit applications.
  • Low Operating Sound Level: Upward airflow directs normal operating noise away from living areas. A rigid top panel isolates motor sound, and isolator-mounted compressors with rippled condenser coil fins muffle fan motor and compressor operating sounds.
  • U.L. and C.U.L. Listed: Approved for outdoor application.
  • Certified: In accordance with the Unitary Small Equipment certification program, based on ARI Standard 210/240.

Maintenance Features:

  • Low Maintenance: Permanently lubricated motor bearings eliminate the need for annual servicing.
  • Easy Service Access: Fully exposed refrigerant connections and a single panel covering electrical controls simplify unit servicing.
  • Secured Service Valves: Re-usable service valves are provided on both liquid and vapor sweat connections for easy evacuation and charging.

Warranty:

  • Single Phase Units: 5-year limited parts warranty and 5-year limited compressor warranty.

Accessories (Optional):

  • Start Assist Kit (2SA067):* May be required for 42, 48, and 60 models (factory installed on 18, 24, 30, 36 models).
  • Blower Time Delay: Increases efficiency by maintaining blower operation for approximately one minute after cooling thermostat is satisfied.
  • Hard Start Kits: Provides necessary starting torque for use with Thermal Expansion Valve Kit.
  • Low Temperature Cutout (2LT06700224): Prevents heat pump operation below -10°F ambient temperature.
  • Compressor Blanket: Reduces normal operating sound.
  • Add-on Fossil Fuel Control: Interface controls for use with gas/oil furnaces and heat pump systems.
  • Thermal Expansion Valve Kit (1TVM900 Series TXV kit): Improves system performance.
  • Outdoor Thermostat (2TD06700124): Provides additional staging of supplemental electric heat.
  • Room Thermostats: A selection of matching thermostats offering features like 2H/1C manual changeover, 3H/2C non-programmable digital, and 3H/2C auto/manual changeover electronic programmable 7-day hardwire thermostats.

York THGD18 THRU 60 Specifications