Loading...
5168274-BIM-I-1121
Johnson Controls Ducted Systems 17
Table 6: Electrical Data
XA-15, XA-20 - Standard Drive Without Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat
(Field Installed Accessory Only)
MCA
1
(Amps)
Max Fuse
2
/
Breaker
3
Size
(Amps)
RLA LRA MCC FLA FLA FLA Model kW Stages Amps
-15
(15)
208-3-60 25 164 39 4.1 13.5 0
NONE - - - 78 100
E18 13.5 1 37.5 124.8 125
E36 27 2 74.9 124.8 125
E54 40.6 2 112.7 157.7 175
E72 54.1 2 150.2 171.6 200
230-3-60 25 164 39 3.9 13 0
NONE - - - 77.1 100
E18 18 1 43.3 131.2 150
E36 36 2 86.6 131.2 150
E54 54 2 129.9 146.2 175
E72 72 2 173.2 189.5 225
460-3-60 12.2 100 19 2.15 6.5 0
NONE - - - 38.3 50
E18 18 1 21.7 65.3 70
E36 36 2 43.3 65.3 70
E54 54 2 65 73.1 80
E72 72 2 86.6 94.7 110
575-3-60 9 78 14 1.6 5.2 0
NONE - - - 28.7 35
E18 18 1 17.3 50.3 60
E36 36 2 34.6 50.3 60
E54 54 2 52 58.5 70
E72 72 2 69.3 75.8 90
-20
(20)
208-3-60 34.3 239 52 3.4 20
NONE - - - 110.8 125
E18 13.5 1 37.5 157.7 175
E36 27 2 74.9 157.7 175
E54 40.6 2 112.7 165.9 175
E72 54.1 2 150.2 204.4 225
230-3-60 3.4 19.4
NONE - - - 110.2 125
E18 18 1 43.3 164.3 175
E36 36 2 86.6 164.3 175
E54 54 2 129.9 164.3 175
E72 72 2 173.2 218.5 225
460-3-60 17.9 125 28 1.8 9.7
NONE - - - 57.2 70
E18 18 1 21.7 84.3 90
E36 36 2 43.3 84.3 90
E54 54 2 65 84.3 90
E72 72 2 86.6 111.3 125
575-3-60 12.8 80 20 1.4 7.8
NONE - - - 42.2 50
E18 18 1 17.3 63.8 70
E36 36 2 34.6 63.8 70
E54 54 2 52 63.8 70
E72 72 2 69.3 85.5 90
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.