SECTION 7 – UNIT CONTROLS
FORM 150.67-NM1
ISSUE DATE: 4/28/2017
7
N U M B E R O F F A N S
P E R S Y S T E M = X
The NUMBER OF FANS PER SYSTEM must be pro-
grammed as needed to match the number of fans on
each system.
S Y S X T R I P V O L T S
= X . X V O L T S
U N I T T R I P V O L T S
= X . X V O L T S
Depending on the option, the trip voltage for a
specific system or unit high current trip can be
programmed. It also calibrates the current read-
out under the OPER DATA key. The approximate
programmed value is calculated using the following
formulas.
System Trip Volts
For individual system high current trip programming
on chillers:
• Add the sum of the compressor and fan RLAs in
the system.
• Multiply the sum by 1.25.
• Divide by 225A.
• The resulting voltage is the value that should be
programmed.
For example, if fan and compressor RLAs total 100A:
5V x 100A
225A
x 1.25 =
625VA
=
225A
2.8V
The programmed value will be 2.8V. A similar calcula-
tion and programming will be necessary for the other
system in a 2-system chiller.
Unit Trip Volts
For total chiller high current trip programming on
460VAC chillers:
• Add the sum of all the compressor and fan RLAs
in the chiller.
• Multiply the sum by 1.25.
• Divide by 225A.
• The resulting voltage is the value that should be
programmed.
For example, if fan and compressor RLAs total 180A:
5V x 180A
225A
x 1.25 =
225A
1125VA
= 5.0V
The programmed value will be 5.0V.
R E M O T E U N I T I D
P R O G R A M M E D = X
When communications is required with a BAS or Op-
tiView Panel, individual unit IDs are necessary for
communications with specific chillers on a single RS-
485 line. ID 0-7 is selectable.