PERFORMANCE DATA - 2 TON
CONDENSER-ONLY DATA (OUTDOOR UNIT)
MODEL
SATURATED SUCTION
AT COMPRESSOR
Outdoor Ambient Temperature
65 °F 75 °F 85 °F 95 °F 105 °F 115 °F 125 °F
T (°F) P (PSIG) MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW
YEE24B21S
35 107 22.0 1.25 20.6 1.41 19.0 1.57 17.6 1.77 15.9 2.25 14.0 2.23 12.0 2.50
40 119 24.6 1.26 23.0 1.42 21.3 1.58 19.6 1.78 17.7 2.26 15.8 2.24 13.6 2.51
45 130 27.1 1.26 25.3 1.42 23.5 1.59 21.7 1.79 19.6 2.28 17.5 2.25 15.1 2.51
50 143 29.6 1.27 27.7 1.43 25.7 1.61 23.7 1.81 21.5 2.29 19.2 2.26 16.7 2.52
55 156 32.2 1.27 30.1 1.44 27.9 1.62 25.8 1.82 23.4 2.30 20.9 2.27 18.3 2.53
Notes:
1. For Outdoor Unit (Condenser) performance only. Data does not include the effects of air handler power or heat.
2. Performance based on 15ºF subcooling and 15ºF superheat at the Outdoor Unit base valves.
a. Increase capacity by 1% for each 2ºF increase in subcooling.
b. Decrease capacity by 1% for each 2ºF decrease in subcooling.
3. Maximum recommended condensing temperature is 140ºF.
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. YEE24B21S
AIR TEMPERATURE
ENTERING
OUTDOOR UNIT (°F)
IDCFM 600 800 1000
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
55
T.C. 22.6 24.8 24.7 27.2 29.7 24.3 25.9 25.8 28.3 30.7 26.2 27.0 26.9 29.4 31.7
S.C. 22.6 19.9 16.7 16.7 13.8 24.3 23.1 18.1 18.8 14.9 26.2 26.2 19.6 20.8 16.0
KW 1.4 1.4 1.4 1.3 1.3 1.4 1.4 1.4 1.4 1.4 1.5 1.5 1.5 1.5 1.4
65
T.C. 21.8 23.8 23.7 26.2 28.7 23.5 24.8 24.8 27.2 29.6 25.2 25.8 25.8 28.2 30.6
S.C. 21.8 19.6 16.4 16.6 13.5 23.5 22.5 18.1 18.7 14.7 25.2 25.4 19.8 20.8 15.9
KW 1.5 1.5 1.5 1.5 1.5 1.6 1.6 1.6 1.6 1.5 1.6 1.6 1.6 1.6 1.6
75
T.C. 21.0 22.7 22.7 25.1 27.5 22.6 23.7 23.6 26.0 28.5 24.3 24.6 24.6 26.9 29.4
S.C. 21.0 19.1 16.1 16.3 13.2 22.6 21.8 18.0 18.5 14.4 24.3 24.5 19.8 20.7 15.7
KW 1.7 1.7 1.7 1.7 1.7 1.8 1.8 1.8 1.8 1.7 1.8 1.8 1.8 1.8 1.8
85
T.C. 20.2 21.5 21.5 23.9 26.3 21.6 22.5 22.4 24.7 27.2 23.3 23.4 23.3 25.6 28.0
S.C. 20.2 18.6 15.7 15.9 12.8 21.6 21.0 17.7 18.2 14.1 23.3 23.4 19.7 20.5 15.4
KW 1.9 1.9 1.9 1.9 1.9 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.1 2.0 2.0
95
T.C. 19.2 20.3 20.4 22.6 24.9 20.6 21.3 21.2 23.4 25.7 22.2 22.2 22.0 24.1 26.6
S.C. 19.2 18.0 15.3 15.5 12.3 20.6 20.1 17.3 17.8 13.7 22.2 22.2 19.4 20.0 15.0
KW 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.3 2.3 2.3 2.3 2.3
105
T.C. 18.2 19.1 19.1 21.2 23.5 19.6 20.0 19.8 21.9 24.2 21.1 20.9 20.5 22.6 24.9
S.C. 18.2 17.3 14.7 15.0 11.8 19.6 19.1 16.8 17.2 13.1 21.1 20.9 18.9 19.4 14.4
KW 2.4 2.4 2.4 2.5 2.4 2.5 2.5 2.5 2.5 2.5 2.6 2.6 2.6 2.6 2.6
115
T.C. 17.2 17.8 17.9 19.8 21.9 18.5 18.7 18.5 20.4 22.5 20.0 19.6 19.0 21.0 23.2
S.C. 17.2 16.6 14.1 14.3 11.2 18.5 18.1 16.2 16.5 12.5 20.0 19.6 18.3 18.6 13.8
KW 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.9 2.9 2.9 2.9 2.9
125
T.C. 16.1 16.5 16.5 18.3 20.3 17.3 17.4 17.0 18.8 20.8 18.8 18.3 17.5 19.2 21.2
S.C. 16.1 15.7 13.3 13.5 10.5 17.3 17.0 15.4 15.6 11.7 18.8 18.3 17.5 17.7 12.9
KW 3.1 3.1 3.1 3.1 3.1 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.3 3.2
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (OUTDOOR AND INDOOR).
Green shaded cells are ACCA (TVA) conditions.
Blue shaded cells are AHRI conditions.