Supply static after indoor coil (in w.c.")
Return Static (in w.c.") before lter
Total External Static Pressure
Low
1 2
Medium Low Medium
3 4
Medium High High
5
A B DC
A B C D
Air Side: System Total External Static Pressure
Supply static before indoor coil (in w.c.")
Return Static (in w.c.") after lter (furnace side)
Cooling
&
Heat Pump
Indoor
Blower Set-Up
COOL
ADJUST
ECM
X-13
PSC
A B C D
DELAY
Supplementary
Heating
Indoor
Blower Set-Up
ECM
X-13
PSC
A
1 5
High
2 3 4
Low
Medium
Low
Medium
Medium
High
D
B C
Outside Air:
Dry Bulb
Temperature DropReturn Air:
Dry Bulb
Supply Air:
Dry Bulb
Wet BulbWet Bulb
Temperature Rise
Defrost Control Board
Demand DefrostYorkGuard VI Time and Temperature
Maximum Rated ESP (in w.c.")
Low Temp Cut Out Balance Point Defrost Curve Y2 Lock FFUEL Switch Point
Hot Heat Pump
Fill in the information ie.. "ON", "OFF" or the appropriate "Value" for the elds that apply to the defrost control board installed
Run Time: Time and Temperature board only 30, 60 or 90 minutesBonnet Sensor Present
HEAT
Refrigerant Charge and Metering Device
TXV Fixed OriceR-410A
Oz.
# 45s# Elbows
TXV #
Orice Size Liquid Line Temp
Subcooling
Superheat
High Side Pressure Low Side PressureSuction Line Temp
Additional Lineset Length Adder per foot - lbs.
Total Added - lbs. Oz.
Cycle Test
Operate the unit through several heating cycles from the thermostat, noting and correcting any problems
Operate the unit through continuous fan cycles from the thermostat, noting and correcting any problems
Operate the unit through a cooling cycles, noting and correcting any problems
Operate the unit through an emergency heating cycles, noting and correcting any problems
Installation debris disposed of and indoor and outdoor areas cleaned up?
Clean Up
Page 2 of 2
Owner Education
Explain operation of system to equipment owner
Explain the importance of regular lter replacement and equipment maintenance
Provide owner with the owner's manual
Explain thermostat use and programming (if applicable) to owner
Comments Section
Return Air:
Dry Bulb
Supply Air:
Dry Bulb
Wet BulbWet Bulb