EasyManua.ls Logo

York YHJD30S41S4 - Cooling Capacity - Upflow, Downflow & Horizontal Furnaces and Coils (Coil Only Ratings)

York YHJD30S41S4
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
571209-YTG-C-1012
6 Johnson Controls Unitary Products
MA Modular Air Handlers use Coil Only Ratings.
PSC furnaces, such as the TG8S, TGLS, and TG9S, use Coil Only Ratings.
COOLING CAPACITY - Upflow, Downflow & Horizontal Furnaces and Coils (Coil Only Ratings)
UNIT MODEL
COIL
CFM RANGE
(Min.-max.)
COOLING
MODEL WIDTH
RATED
CFM
NET MBH
SEER
1
EER
TOTAL SENS.
13 SEER HP COIL ONLY RATINGS
YHJD18S41S2
FC/MC/PC18 14.5,17.5 450 - 750 600 18.0 14.0 13.00 11.00
FC/MC/PC24 14.5,17.5 450 - 750 600 18.0 14.0 13.50 11.00
FC/MC/PC30 14.5,17.5 450 - 750 600 18.0 13.7 13.00 11.00
UC24 14.5,17.5 450 - 750 600 18.0 13.8 13.05 11.00
UC30 14.5,17.5 450 - 750 600 18.0 13.8 13.05 11.00
YHJD24S41S4
FC/MC/PC32 14.5 600 - 1000 800 23.8 17.1 13.00 11.00
FC/MC/PC35 17.5,21.0 600 - 1000 800 23.6 17.1 13.00 11.00
FC/MC/PC37 14.5 600 - 1000 800 24.0 17.3 13.00 11.00
FC/MC/PC43 17.5,21.0 600 - 1000 800 24.0 17.3 13.00 11.00
YHJD30S41S4
FC/MC/PC32 14.5 800 - 1200 1000 29.8 21.8 13.00 11.00
FC/MC/PC35 17.5,21.0 800 - 1200 1000 29.8 21.8 13.00 11.00
FC/MC/PC37 14.5 800 - 1200 1000 30.0 22.2 13.00 11.00
FC/MC/PC43 17.5,21.0 800 - 1200 1000 30.0 22.2 13.00 11.00
YHJD36S41S4
FC/MC/PC37 14.5 1000 - 1400 1200 36.0 26.8 13.00 11.00
FC/MC/PC43 17.5,21.0 1000 - 1400 1200 36.0 26.6 13.00 11.00
FC/MC/PC48 21.0,24.5 1000 - 1400 1200 36.0 26.6 13.00 11.00
UC48 21.0,24.5 1000 - 1400 1200 36.0 26.8 13.00 11.00
YHJD42S41S4
FC/MC/PC60 21.0,24.5 1200 - 1600 1400 41.0 31.8 13.00 11.00
UC60 21.0,24.5 1200 - 1600 1400 40.5 31.0 13.00 11.00
YHJD48S41S4
FC/MC/PC60 21.0,24.5 1400 - 1800 1600 44.0 33.4 13.00 11.00
FC/MC62 24.5 1400 - 1800 1600 44.5 33.8 13.00 11.00
UC60 21.0,24.5 1400 - 1800 1600 44.0 32.8 13.00 11.00
YHJD60S41S5
FC/MC62 24.5 1600 - 2000 1800 57.5 41.0 13.25 11.35
FC64 24.5 1600 - 2000 1800 56.5 42.5 13.00 11.00
1. Requires a S1-2FD06700224 Blower Time Delay unless a standard furnace is equipped with one.
COOLING CAPACITY - With High Efficiency Motor Furnaces
UNIT
MODEL
FURNACE
COIL
MODEL
1
COOLING
MODEL WIDTH
RATED
CFM
Net MBH
SEER EER
TOTAL SENS.
13 SEER HP WITH HIGH EFFICIENCY MOTOR FURNACES
2
YHJD18S41S2
T*(8,L)V*A12 14.5 FC/MC/PC18A 620 18.0 12.3 14.50 12.30
T*(8,L)V*A12 14.5 FC/MC/PC24A 640 18.0 12.7 14.80 12.50
T*(8,L)V*A12 14.5 FC/MC/PC30A 640 18.0 12.7 14.80 12.50
T*(8,L)V*A12 14.5 UC18A 620 18.0 12.4 14.60 12.30
T*(8,L)V*A12 14.5 UC24A 640 18.0 12.8 14.80 12.50
T*(8,L)V*A12 14.5 UC30A 640 18.0 12.8 14.80 12.50
T*(8,L)V*B12 14.5 FC/MC/PC18A 620 18.0 12.3 14.50 12.30
T*(8,L)V*B12 17.5 FC/MC/PC24B 575 18.0 12.2 14.90 12.60
T*(8,L)V*B12 17.5 FC/MC/PC30B 575 18.0 12.2 14.90 12.60
T*(8,L)V*B12 17.5 UC18B 580 18.0 12.0 14.60 12.30
T*(8,L)V*B12 17.5 UC24B 575 18.0 12.3 14.90 12.60
T*(8,L)V*B12 17.5 UC30B 575 18.0 12.3 15.00 12.60
T*(8,L)X*A12 14.5 FC/MC/PC18A 540 18.0 14.3 14.00 12.00
T*(8,L)X*A12 14.5 FC/MC/PC24A 595 18.0 14.9 14.00 12.00
T*(8,L)X*A12 14.5 FC/MC/PC30A 595 18.0 14.9 14.00 12.00
T*(8,L)X*A12 14.5 UC18B 590 18.0 13.9 14.50 12.00
For Notes See Page 12.