561923-YTG-E-0613
Johnson Controls Unitary Products 31
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 °F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
COOLING PERFORMANCE DATA
CONDENSING UNIT MODEL NO. YHJF48S41S1
INDOOR COIL MODEL NO. F6FP060
CONDENSING
ENTERING AIR
TEMPERATURE
IDCFM 1400 1600 1800
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
65
T.C.
46.3 48.5 48.5 53.1 57.3 48.0 50.1 49.9 53.5 58.0 49.8 51.6 51.4 53.9 58.7
S.C.
46.3 42.2 35.8 35.4 29.2 48.0 45.7 38.1 36.7 29.9 49.8 49.3 40.4 38.0 30.6
KW
2.67 2.73 2.72 2.76 2.74 2.77 2.80 2.80 2.81 2.80 2.87 2.87 2.87 2.86 2.87
75
T.C.
44.4 46.1 46.1 50.7 55.0 46.2 47.4 47.3 51.3 55.8 48.0 48.7 48.5 51.8 56.5
S.C.
44.4 41.2 34.8 34.4 28.2 46.2 44.2 37.0 36.0 29.0 48.0 47.1 39.2 37.5 29.8
KW
3.00 3.04 3.04 3.05 3.09 3.10 3.12 3.12 3.13 3.16 3.20 3.20 3.20 3.21 3.23
85
T.C.
42.4 43.6 43.6 48.3 52.7 44.3 44.7 44.7 49.0 53.5 46.2 45.7 45.7 49.8 54.3
S.C.
42.4 40.2 33.7 33.5 27.1 44.3 42.6 35.8 35.3 28.0 46.2 45.0 38.0 37.0 29.0
KW
3.33 3.35 3.35 3.34 3.44 3.43 3.44 3.44 3.45 3.52 3.54 3.53 3.53 3.56 3.60
95
T.C.
40.5 41.1 41.2 45.9 50.5 42.5 42.0 42.0 46.8 51.3 44.4 42.8 42.8 47.7 52.1
S.C.
40.5 39.2 32.7 32.6 26.0 42.5 41.0 34.7 34.6 27.1 44.4 42.8 36.8 36.5 28.2
KW
3.66 3.66 3.66 3.63 3.80 3.76 3.76 3.76 3.77 3.88 3.87 3.86 3.86 3.91 3.97
105
T.C.
37.9 38.3 37.6 42.7 47.5 39.7 39.5 38.5 43.5 48.2 41.5 40.7 39.3 44.3 48.8
S.C.
37.9 37.4 31.1 31.4 24.8 39.7 39.1 33.2 33.3 25.9 41.5 40.7 35.3 35.3 26.9
KW
4.05 4.05 4.04 4.10 4.22 4.17 4.17 4.13 4.21 4.30 4.29 4.28 4.23 4.33 4.38
115
T.C.
35.2 35.5 34.0 39.5 44.6 36.9 37.1 34.9 40.2 45.1 38.7 38.7 35.8 41.0 45.5
S.C.
35.2 35.5 29.6 30.1 23.6 36.9 37.1 31.7 32.1 24.7 38.7 38.7 33.9 34.1 25.7
KW
4.44 4.44 4.42 4.57 4.64 4.57 4.58 4.51 4.66 4.71 4.70 4.71 4.60 4.75 4.78
125
T.C.
32.6 32.7 30.4 36.3 41.7 34.2 34.7 31.3 37.0 42.0 35.8 36.6 32.2 37.7 42.3
S.C.
32.6 32.7 28.0 28.8 22.4 34.2 34.7 30.2 30.9 23.5 35.8 36.6 32.2 32.9 24.5
KW
4.83 4.83 4.80 5.05 5.06 4.98 4.98 4.88 5.11 5.12 5.12 5.14 4.97 5.17 5.19
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (OUTDOOR + INDOOR).
Air Handler Coil T.C. S.C. KW
–
FC/MC62 1.00 1.01 1.04
AHE60D – 1.01 1.03 0.97
AHR60D – 1.01 1.03 1.03
AHV60D – 1.01 1.02 1.00
MV20D FC/MC62D 1.01 1.03 0.98
MV20D FC64D 1.05 1.07 0.98
MX20D FC/MC62D 1.03 1.03 0.96
MX20D FC64D 1.06 1.08 0.97
Furnace Coil T.C. S.C. KW
T*(8,L)V*C16 FC/MC62D 1.00 1.02 1.01
T*(8,L)V*C16 FC64D 1.05 1.06 1.02
T*(8,L)V*C20 FC/MC62D 1.01 1.02 1.00
T*(8,L)V*C20 FC64D 1.05 1.06 1.00
T*(8,L)X*C16 FC/MC62D 1.01 1.02 1.00
T*(8,L)X*C16 FC64D 1.05 1.06 1.00
T*(8,L)X*C20 FC/MC62D 1.04 1.06 0.99
T*(8,L)X*C20 FC64D 1.05 1.06 0.99
T*9(C,V)*C16 FC/MC62D 1.00 1.02 1.01
T*9(C,V)*C16 FC64D 1.05 1.06 1.02
T*9(C,V)*C20 FC/MC62D 1.01 1.05 1.02
T*9(C,V)*C20 FC64D 1.04 1.05 1.03
T*9(C,V)*D20 FC/MC62D 1.00 1.02 1.02
T*9(C,V)*D20 FC64D 1.04 1.06 1.02
T*9X*C16 FC/MC62D 1.01 1.02 1.00
T*9X*C16 FC64D 1.05 1.06 1.00
T*9X*C20 FC/MC62D 1.01 1.02 1.00
T*9X*C20 FC64D 1.05 1.06 0.99
T*9X*D20 FC/MC62D 1.00 1.02 1.00
T*9X*D20 FC64D 1.05 1.06 1.01
Y*(8,L)C*C16 FC/MC62D 1.00 1.02 1.01
Y*(8,L)C*C16 FC64D 1.05 1.06 1.02
Y*(8,L)C*C20 FC/MC62D 1.01 1.02 1.00
Y*(8,L)C*C20 FC64D 1.05 1.06 1.00
Y*9C*C16 FC/MC62D 1.00 1.02 1.01
Y*9C*C16 FC64D 1.05 1.06 1.02
Y*9C*C20 FC/MC62D 1.01 1.05 1.02
Y*9C*C20 FC64D 1.04 1.05 1.03
Y*9C*D20 FC/MC62D 1.00 1.02 1.02
Y*9C*D20 FC64D 1.04 1.06 1.02
Furnace Coil T.C. S.C. KW