JOHNSON CONTROLS
10
FORM 100.50-SU3 (1207)
STAND ALONE CONTROL HEATING
Field Wiring
No additional connections required.
Misc. Connections
No additional connections required.
Programming
“HEATING MODE OPERATION ENABLED” – Must
be set to ON using Parameter 54 under the PROGRAM
key on the Simplicity control board or under the
HEATING SETUP tab in the Simplicity PC software
package.
“CV OCCUPIED HEATING SETPOINT” – Must be
set using Parameter 11 under the PROGRAM key on
the Simplicity control board or under the HEATING
SETUP tab in the Simplicity PC software package.
Settable between 45.0º F and 99.0º F. The default value
is 68.0º F.
“CV UNOCCUPIED HEATING SETPOINT” – Must
be set using Parameter 13 under the PROGRAM key
on the Simplicity control board or under the COOLING
SETUP tab in the Simplicity PC software package.
Settable between 45.0º F and 99.0º F. The default value
is 60.0º F.
“STAGES OF HEATING AVAILABLE” - Must be set
using Parameter 81 under the PROGRAM key on the
Simplicity control board or under the HEATING SETUP
tab in the Simplicity PC software package.