23. For standard top mounted steam condenser, the
harnesses from the main junction box and power
panel are connected directly to the steam condens-
er box after the steam condenser is installed in the
eld.
24. For inlet steam pressures up to 200 PSIG, PT-170
Range is 0-300 PSIG and PT-172 Range is 0-100
PSIG. For inlet steam pressures above 200 PSIG,
PT-170 Range is 0-500 PSIG and PT-172 Range
is 0-150 PSIG.
25. Manual motor protector signaling contact is
closed when operator is in the o or on position,
open when operator is in any tripped position.
Trips may be caused by thermal overload, short
circuit, under-voltage, or shunt.
NOTES (CONT'D)