EasyManua.ls Logo

York YST - User Manual

York YST
164 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
LD12189
MODEL YST
STEAM TURBINE DRIVE CENTRIFUGAL LIQUID CHILLER
WITH OPTIVIEW
TM
CONTROL CENTER
DESIGN LEVEL F AND G
STEAM TURBINE
CENTRIFUGAL LIQUID CHILLERS
OPERATIONS MANUAL Supersedes: 160.67-O1 (114) Form: 160.67-O1 (415)
Issue Date:
April 1, 2015

Table of Contents

Other manuals for York YST

Questions and Answers

  • J
    Justin HillJul 25, 2025
    What to do if the suction pressure is abnormally low in my York YST Chiller?
    • P
      Paula DixonJul 25, 2025
      Low suction pressure in a York Chiller can stem from a few issues. First, check for refrigerant leaks and charge the system if the refrigerant level is insufficient. A subcooler level valve problem could also be the cause; remove any obstructions. Additionally, inspect the evaporator tubes for dirt or restrictions and clean them if necessary. Finally, if the system load is insufficient for its capacity, check the prerotation vane and hot gas valve operation, as well as the setting of the low liquid temperature cutout.
  • K
    Kevin SmithAug 3, 2025
    Why is the discharge pressure abnormally high in my York YST Chiller?
    • S
      Sandra WhiteAug 3, 2025
      High discharge pressure in your York Chiller can be caused by several factors. One potential cause is dirty or scaled condenser tubes. To resolve this, clean the condenser tubes and check the water conditioning. Another cause could be high condenser water temperature, in which case you should reduce the condenser water inlet temperature, checking the cooling tower and water circulation. Finally, insufficient condensing water flow can also lead to this problem; increase the quantity of water through the condenser to the proper value.
  • W
    wolfrhondaAug 14, 2025
    Why is the evaporator pressure high in my York YST?
    • S
      Sierra BrennanAug 14, 2025
      High evaporator pressure in your York Chiller can be caused by prerotation vanes failing to open. Check the prerotation vane motor positioning circuit. Another reason may be system overload. Ensure the vanes are wide open, the hot gas valve is fully closed, and the speed is at maximum. System conditions might require override controls to limit the chiller capacity until the load decreases.

Summary

GENERAL SAFETY GUIDELINES

SAFETY SYMBOLS

Describes symbols used to alert readers to specific situations.

DOCUMENT INFORMATION

Changeability of Document

Discusses document updates and applicability.

Associated Literature

Lists related manuals and their forms.

NOMENCLATURE

SYSTEM DESCRIPTION AND OPERATION

General System Description

Provides an overview of the YORK Model YST Chiller's components and operation.

Refrigeration System Operation

Explains how the chiller cools liquids using refrigerant.

Capacity Controls

Details how the chiller reduces capacity at part load conditions.

Steam and Condensate Flow

Describes the process of steam converting to mechanical energy and condensate flow.

OPTIVIEW CONTROL CENTER INTRODUCTION

Overview and Interface

Introduces the control center, its display, navigation, and access levels.

Analog Input Ranges

Details valid display ranges for analog inputs from York Microboard and Frick I/O.

Key Operational Screens

Describes important screens like Home, Refrigeration, Compressor, Steam System, and Capacity Controls.

Control and Configuration

Covers Capacity Controls, PID Setup, Setpoints, and Configuration screens for system management.

Diagnostics and Logging

Covers History, Security Log, and Trend functions for system analysis.

System Messages

Explains various warning, shutdown, and status messages displayed by the system.

PRINTERS

Printer Overview

Lists reports that can be printed and compatible printer models.

Printer Connections and Setup

Details physical connections and software configuration for printers.

Automatic Data Logging

Explains how to configure automatic printing of status reports.

York YST Specifications

General IconGeneral
BrandYork
ModelYST
CategoryChiller
LanguageEnglish