SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION
REFRIGERATION SYSTEM SCREEN
LD09258
FIGURE 7 - REFRIGERATION SYSTEM SCREEN
NOTE: OptiView
™
 Control Center Screens shown may NOT represent the exact screens according to the software version utilized.
OVERVIEW
This screen gives a general overview of common chill-
er parameters for both refrigeration shells. 
DISPLAY ONLY
Discharge Temperature 
Displays the temperature of the refrigerant in its gas-
eous state at discharge of the compressor as it travels 
to the condenser.
Chilled Liquid Temperature - Leaving
Displays the temperature of the liquid as it leaves the 
evaporator.
Chilled Liquid Temperature - Return
Displays the temperature of the liquid as it enters the 
evaporator.
Chilled Liquid Temperature - Setpoint
Displays the active temperature setpoint to which the 
chiller is controlling the evaporator liquid. This value 
could come from a 0-20mA, 4-20mA, 0-10VDC or 
2-10VDC input in Analog Remote mode, PWM signal 
in Digital Remote mode, MicroGateway interface in 
ISN mode, or a locally programmed value.
Evaporator Pressure 
Displays the present refrigerant pressure in the evaporator.
Evaporator Saturation Temperature 
Displays the present saturation temperature in the 
evaporator. 
Condenser Liquid Temperature - Leaving
Displays the temperature of the liquid as it leaves the 
condenser.
Condenser Liquid Temperature - Return
Displays the temperature of the liquid as it enters the 
condenser.
Condenser Pressure 
Displays the refrigerant pressure in the condenser.
Condenser Saturation Temperature 
Displays the saturation temperature in the condenser.
Oil Sump Temperature
Displays the temperature of the oil in the sump.