SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION
ALARM/SHUTDOWN SETPOINTS SCREEN
   LD09271
FIGURE 35 - ALARM/SHUTDOWN SETPOINTS SCREEN
NOTE: OptiView
™
 Control Center Screens shown may NOT represent the exact screens according to the software version utilized.
OVERVIEW
This screen allows programming of the actuation points 
for various Alarm and Shutdown conditions primarily 
associated with the protection of the turbine and steam 
condenser. If an Alarm Setpoint is exceeded, a Warn-
ing Message will be displayed. If a Shutdown Setpoint 
is exceeded, the chiller will be shutdown immediately 
and a Safety Shutdown Message will be displayed. In 
either case the Audible Alarm on the Power Panel is 
sounded and the Anticipatory Alarm/Safety Shutdown 
contacts on the YORK I/O Board are closed. In order 
to better understand how these setpoints are used in the 
logic, references are made to the applicable page num-
ber of YORK YST Logic Diagram 160.67-M3 where 
the setpoint has visibility. To view the graphics asso-
ciated with the setpoint, the applicable Screen name 
is also referenced. All setpoints require a login access 
level of Service or higher. 
PROGRAMMABLE
HLSP2 – Hotwell High Level Shutdown
    Screen:  Condensate
Range: 80-100 % Default: 90 %
An immediate shutdown is initiated if the Hotwell 
Level Transmitter input signal remains continuously 
above this setpoint for the TDSP13-Hotwell High 
Level Timeout delay shown on the Time Delay Alarm/
Shutdown Setpoints Screen.
PSP7 - Turbine Exhaust Steam High Pressure 
Shutdown
    Screen:  Steam System
Range: 2.5-7.5 PSIA Default: 3.5 PSIA
An immediate shutdown is initiated if the input signal 
from the Turbine Exhaust Steam Pressure Transmitter 
remains continuously  above this setpoint for the 
TDSP7-Turbine Exhaust High Pressure Timeout delay 
shown on the Time Delay Alarm/Shutdown Setpoints 
Screen. This check is bypassed until the chiller is in the 
"System Run" mode.
PSP8 - Turbine Supply Oil Low Pressure 
Shutdown
    Screen:  Turbine
Range: 6.0-10.0 PSIG Default: 6.0 PSIG