SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION
FORM 160.67-O1 
ISSUE DATE: 4/1/2015
2
TIME DELAY ALARM/SHUTDOWN SETPOINTS SCREEN
   LD09277
FIGURE 36 - TIME DELAY ALARM/SHUTDOWN SETPOINTS SCREEN
NOTE: OptiView
™
 Control Center Screens shown may NOT represent the exact screens according to the software version utilized.
OVERVIEW
This screen allows programming of the time delays for 
various Alarm and Shutdown conditions primarily as-
sociated with the protection of the turbine and steam 
condenser. To view the graphics associated with the 
setpoint, the applicable Screen name is also referenced. 
All setpoints require a login access level of Service or 
higher. 
PROGRAMMABLE
TDSP1 – Excessive Slow Roll Timeout 
    Screen: Steam System 
Range: 0-2700 Sec Default: 1200 Sec
An immediate shutdown is initiated if the turbine has 
been slow rolling longer than the calculated slow roll 
warm-up time plus this delay. 
TDSP7 - Turbine Exhaust High Pressure 
Timeout
    Screen: Steam System 
Range: 0-1800 Sec Default: 600 Sec
An immediate shutdown is initiated if the input signal 
from the Turbine Exhaust Steam Pressure Transmitter 
remains continuously above the PSP7-Turbine Exhaust 
Steam High Pressure Shutdown setpoint shown on the 
Alarm/Shutdown Setpoints Screen for this delay after 
the chiller is in the "System Run" mode.
TDSP8 – Excessive Start Delay Timeout
    Screen: Steam System 
Range: 0-2700 Sec Default: 1200 Sec
An immediate shutdown is initiated if the system 
prelube has been completed but the operator has failed 
to press the Begin Slow Roll key on the Steam System 
Screen to initiate the slow roll warm-up within this de-
lay. 
TDSP13 – Hotwell High Level Timeout
    Screen: Condensate 
Range: 0-60 Sec Default: 10 Sec
An immediate shutdown is initiated if the Hotwell Lev-
el Transmitter input signal remains continuously above 
the HLSP2 – Hotwell High Level Shutdown shown 
on the Alarm/Shutdown Setpoints Screen or the steam 
condenser hotwell high-level switch input to the York 
I/O board has been continuously open for this delay.
TDSP15 – Turbine Mechanical Trip Timeout
    Screen: Turbine
Range: 5-2400 Sec Default: 10 Sec