SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION
ADVANCED TREND SETUP SCREEN
Primary Trigger, Operator
& Test
Primary to Secondary
Operator
Secondary Trigger,
Operator & Test
Trigger Action
Trigger Delay
FIGURE 52 - ADVANCED TREND SETUP SCREEN
00474vip
NOTE: OptiView
Control Center Screens shown may NOT represent the exact screens according to the software version utilized.
OVERVIEW
The desired data collection start/stop triggers are setup
on this screen. The trend data collection can be set to
start or stop based upon the status of up to two selected
Triggers.
The Triggers can consist of digital events or analog pa-
rameters compared to thresholds. The Triggers can be
used individually or in combination. The digital and
analog parameters are selected from the Common Slots
Screen (or Master Slot Numbers List in this manual).
The parameter selected as the Primary Trigger is com-
pared to a value selected as the Primary Test, using the
Primary Operator as a comparator. If it is evaluated as
true, then the data collection is started or stopped (af-
ter any selected Trigger delay) per the selected Trigger
Action.
A Secondary Trigger can be evaluated with the Prima-
ry Trigger to start/stop data collection. The Primary to
Secondary Operator is used to define the Trigger com-
binations required to be true to start/stop data collec-
tion. The Secondary Trigger is setup and evaluated the
same as the Primary Trigger.
Entry fields are as follows:
If Primary Trigger
Is Primary Operator Primary Test
Primary to Secondary Operator
Secondary Trigger
Is Secondary Operator Secondary Test
Then Trigger Action the Data Collection
With a delay of Trigger Delay
After the desired Triggers are set, the START key on
the TREND Screen must be manually pressed before
the triggers will be evaluated. While waiting for the
triggers to start or stop data collection, a status message
is displayed in the upper right corner of the TREND
Screen describing the pending action.
DISPLAY ONLY
None
PROGRAMMABLE
Primary Trigger
Access Level Required: OPERATOR
Selects the first parameter to be evaluated. Selection is
made from the Slot Numbers listing on the Trend Com-
mon Slots Screen or the Master Slot Numbers List in
this book. Setting this slot number to zero disables the
Primary Trigger.