JOHNSON CONTROLS
126
FORM 160.67-O1 
ISSUE DATE: 4/1/2015
SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION
ADVANCED TREND SETUP SCREEN
Primary Trigger, Operator 
& Test
Primary to Secondary 
Operator
Secondary Trigger, 
Operator & Test
Trigger Action
Trigger Delay
FIGURE 52 - ADVANCED TREND SETUP SCREEN
00474vip
NOTE: OptiView
™
 Control Center Screens shown may NOT represent the exact screens according to the software version utilized.
OVERVIEW
The desired data collection start/stop triggers are setup 
on this screen. The trend data collection can be set to 
start or stop based upon the status of up to two selected 
Triggers. 
The Triggers can consist of digital events or analog pa-
rameters compared to thresholds. The Triggers can be 
used individually or in combination. The digital and 
analog parameters are selected from the Common Slots 
Screen (or Master Slot Numbers List in this manual). 
The parameter selected as the Primary Trigger is com-
pared to a value selected as the Primary Test, using the 
Primary Operator as a comparator. If it is evaluated as 
true, then the data collection is started or stopped (af-
ter any selected Trigger delay) per the selected Trigger 
Action.  
A Secondary Trigger can be evaluated with the Prima-
ry Trigger to start/stop data collection. The Primary to 
Secondary Operator is used to define the Trigger com-
binations required to be true to start/stop data collec-
tion. The Secondary Trigger is setup and evaluated the 
same as the Primary Trigger. 
Entry fields are as follows: 
If Primary Trigger 
Is Primary Operator  Primary Test 
Primary to Secondary Operator
Secondary Trigger
Is Secondary Operator  Secondary Test
Then Trigger Action the Data Collection
With a delay of Trigger Delay   
After the desired Triggers are set, the START key on 
the TREND Screen must be manually pressed before 
the triggers will be evaluated. While waiting for the 
triggers to start or stop data collection, a status message 
is displayed in the upper right corner of the TREND 
Screen describing the pending action.   
DISPLAY ONLY
None
PROGRAMMABLE
Primary Trigger
Access Level Required: OPERATOR 
Selects the first parameter to be evaluated. Selection is 
made from the Slot Numbers listing on the Trend Com-
mon Slots Screen or the Master Slot Numbers List in 
this book. Setting this slot number to zero disables the 
Primary Trigger.