SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION
OPTIVIEW CONTROL CENTER
LD09284
FIGURE 5 - OPTIVIEW CONTROL CENTER
The OptiView Control Center display is highlighted by
a full screen graphics display. This display is nested
within a standard keypad, and is surrounded by “soft”
keys which are redefined based on the currently dis-
played screen. Eight buttons are available on the right
side of the panel, and are primarily used for navigation
between the system screens. At the base of the display
are 5 additional buttons. The area to the right of the
keypad is used for data entry with a standard numeric
keypad provided for entry of system setpoints and lim-
its.
The Decimal key provides accurate entry of
setpoint values.
A +/- key has also been provided to allow entry
of negative values and AM/PM selection dur-
ing time entry.
In order to accept changes made to the chiller
setpoints, the Check key is provided as a uni-
versal ‘Enter key or ‘Accept’ symbol.
In order to reject entry of a setpoint or dismiss
an entry form, the ‘X’ key is provided as a uni-
versal ‘Cancel’ symbol.
Cursor Arrow keys allow
movement on screens which
contain a large amount of entry
data. These keys can also be
used to scroll through history
and event logs.
The Start/Stop control is operated via a three-position
rocker switch. When toggled all the way to the right, it
is considered in the STOP/RESET position. When in
the middle position, this is considered the RUN state.
When toggled to the left-most position, it is considered
in the START state. Each state is described in detail
below:
• STOP / RESET (O)
When in this position, the chiller will not run un-
der any condition. For safety reasons, this posi-
tion is required for many maintenance tasks to be
completed (such as proximity probe and vane cal-
ibration). In addition, the switch must be placed
in this state following a Safety shutdown before
the chiller is allowed to restart. This guarantees
that manual intervention has taken place and the
shutdown has been acknowledged.
• START (◄ )
The switch can only remain in this position when
being acted upon by a manual force. Once the user
has released the switch, it automatically reverts to
the RUN position. Generally, this state only oc-
curs momentarily as the operator attempts to lo-
cally start the unit. Once this position has been
sensed, if all fault conditions are cleared, the unit
will enter the system prelube (start sequence).
• RUN (
)
When in this position, the chiller is able to oper-
ate. The switch spring-returns to this state after it
has been toggled to the START position. When
in this state, the chiller is allowed to function nor-
mally, and will also allow the chiller to automati-
cally restart following a Cycling shutdown. The
switch must be in this state to receive a valid re-
mote start signal when operating under a remote
control source.