SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION
FORM 160.67-O1 
ISSUE DATE: 4/1/2015
2
When the Select Control key is set for 
HGV, the tuning parameters entered 
are also used by the HGV Temperature 
Controller.
Evaporator Pressure
Screen:  Capacity Controls
SP (PSP1) Range: 
Water: 25.0-35.0 PSIG
Brine: 6.0-35.0 PSIG
SP (PSP1) Default: 30.0 PSIG
PID Tuning Ranges - P: 0.00-5.00 I: 0.00-5.00 D: 0.00-5.00 
SPD PID Defaults -  P: 2.00 I: 0.95  D: 0.00
PRV PID Defaults -  P: 2.00 I: 2.00  D: 0.00
HGV PID Defaults -  P: 2.00 I: 2.00  D: 0.00
This box displays parameters pertinent to the 
Evaporator Pressure Controller used to maintain the 
refrigerant pressure in the evaporator (PV) at the 
setpoint (SP) during off design operation. The output 
(CV) displayed will decrease to unload the chiller 
if the evaporator refrigerant pressure falls below the 
setpoint. The black text to the right of the data fields 
changes to SPD,  PRV, or HGV depending on the 
mode selected with the Select Control key The green 
Inactive text changes to yellow Active text to display 
if the controller is presently controlling the chiller 
capacity. 
Condenser Pressure 
Screen:  Capacity Controls
SP (PSP2) Range: 130.0-180.0  SP (PSP2) Default: 145.0 PSIG
PID Tuning Ranges - P: 0.00-5.00 I: 0.00-5.00 D: 0.00-5.00 
SPD PID Defaults -  P: 1.00 I: 0.95  D: 0.00
PRV PID Defaults -  P: 2.00 I: 2.00  D: 0.00
HGV PID Defaults -  P: 2.00 I: 2.00  D: 0.00
This box displays parameters pertinent to the 
Condenser Pressure Controller used to maintain 
the refrigerant pressure in the condenser (PV) at the 
setpoint (SP) during off design operation. The output 
(CV) displayed will decrease to unload the chiller if 
the condenser refrigerant pressure increases above the 
setpoint. In some cases, different tuning parameters 
must be entered to match the process response time 
depending on the controlled device. The black text 
to the right of the data fields changes to SPD, PRV, 
or  HGV depending on the mode selected with the 
Select Control key. The green Inactive text changes 
to yellow Active  text to display if the controller is 
presently controlling the chiller capacity.
Hotwell Level 
Screen:  Condensate
SP (HLSP1) Range: 
30.0-70.0% SP (HLSP1) Default: 50.0%
PID Tuning Ranges - P: 0.00-5.00 I: 0.00-5.00 D: 0.00-5.00  O: 40.0-60.0% 
PID Tuning Defaults -  P: 2.79 I: 1.25  D: 0.00 O: 50.0%
This box displays parameters pertinent to the Hotwell 
Level Controller used to maintain the condensate level 
(PV) in the steam condenser within the proportional 
band of 40-60%. With the default tuning parameters 
shown above, the output (CV) will be 50% at the 
setpoint and will decrease from 50-0% as the level 
(PV) increases from 50-60% to open the Overboard 
Valve and close the Recirculation Valve. The green 
text Auto changes to yellow Manual text to show the 
status of the controller output as presently selected on 
the Auto/Manual Screen. 
Subcooler Level 
Screen:  Condensate
SP (LSP) Range: 20.0 - 80.0% SP (LSP1) Default: 50.0%
RR (RRSP10) Range: 
0.1-4.0 %/Sec RR (RRSP10) Default: 0.1%/Sec 
PID Tuning Ranges - P: 0.00-5.00 I: 0.00-5.00 D: 0.00-5.00 
Z1 PID Tuning Defaults -  P: 0.10 I: 2.50  D: 0.00
Z2 PID Tuning Defaults -  P: 0.10 I: 2.50  D: 0.00
This box displays parameters pertinent to the Subcooler 
Level Controller used to maintain the refrigerant 
liquid level (PV) in the subcooler at the setpoint (SP). 
The output (CV) displayed will increase to open the 
Subcooler Level Control Valve if the level increases 
above the setpoint. On startup, after the TDSP6-Time 
Delay/Subcooler Level Pulldown has elapsed, the 
level setpoint is set from 0% to the present level and 
then ramped up to the programmed setpoint at the 
programmed setpoint ramp rate (RR) displayed. The 
output (CV) will begin to decrease from 100% to close 
the valve and begin backing liquid up in the subcooler 
until the setpoint is achieved. The output (CV) will 
never be allowed to decrease below the LCVM-
Subcooler Level Valve Minimum Position shown on 
Capacity Control Setpoints Screen 1. The green Auto 
text changes to yellow Manual text to show the status 
of the controller output as presently selected on the 
Auto/Manual Screen. The black text to the right of the 
data fields changes to Z1 or Z2 depending on the zone 
selected with the Select Zone key.