SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION
STEAM SYSTEM SCREEN - AUTO START
LD09259
FIGURE 17 - STEAM SYSTEM SCREEN - AUTO START
NOTE: OptiView
™
 Control Center Screens shown may NOT represent the exact screens according to the software version utilized.
OVERVIEW
This screen displays information pertaining to the 
turbine and steam condenser and shows all steam pa-
rameters and the status of turbine and steam control 
devices. The cooling liquid flow lines are animated 
whenever adequate flow has been established to close 
the refrigerant condenser liquid flow switch contacts. 
The turbine steam inlet flow line is animated at speeds 
above 500 RPM.
DISPLAY ONLY
Turbine Speed 
The turbine speed is sensed by two magnetic pickups 
that monitor a toothed gear installed on the turbine 
shaft. The pickup signals are converted to 4-20 mA 
signals by frequency-to-analog converters in the Tur-
bine Box and connected to the Analog I/O Board in the 
Control Center.  This data field displays the highest of 
the two speed input signals. 
Speed Setpoint
Displays the current speed setpoint that is dictated by 
the startup logic during the slow roll warm-up and 
ramp up to rated speed. After the chiller has attained 
minimum rated speed, the capacity control logic deter-
mines this setpoint.
Steam Flow  
Displays the rate of steam flowing through the turbine. 
This text and data field only appears if FSE1-Steam 
Flow Sensor Enable is set for Enabled on Configura-
tion Screen 2. 
Exhaust Pressure
Displays the steam pressure measured at the exhaust 
of the turbine. 
First Stage Pressure
Displays the steam pressure measured in the first stage 
of the turbine. This text and data field only appears if 
MSSP15-Turbine First Stage Pressure Sensor is set for 
Enabled on Configuration Screen 1. 
Inlet Pressure
Displays the steam pressure measured at the inlet of 
the turbine.
Inlet Temperature
Displays the steam temperature measured at the inlet 
of the turbine.
Leaving Steam Condenser Liquid 
Temperature
Displays the cooling liquid temperature measured at 
the outlet of steam condenser