SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION
RAMP RATE SETPOINTS SCREEN
   LD09283
FIGURE 43 - RAMP RATE SETPOINTS SCREEN
NOTE: OptiView
™
 Control Center Screens shown may NOT represent the exact screens according to the software version utilized.
Time Setpoints
Access Level Required: VIEW 
Moves to a sub-screen that allows programming of 
various time delays pertaining to the operation of the 
chiller.
Ramp Rate Setpoints
Access Level Required: VIEW 
Moves to a sub-screen that allows programming of 
various speed setpoint and valve control signal ramp 
rates pertaining to the operation of the chiller.
OVERVIEW
This screen allows programming of various speed 
setpoint and control valve ramp rates pertinent to the 
operation of the chiller and the optional equipment 
supplied. It is also a gateway to screens for program-
ming pressures, time delays, and speeds pertinent to 
the operation of the chiller. To view the results of a 
setpoint change, the applicable Screen name is also ref-
erenced. All setpoints require a login access level of 
Service or higher.
PROGRAMMABLE
RRSP3 – Slow Roll Speed Setpoint
    Screen: Steam System
Range: 25-100 RPM/Sec Default: 50 RPM/Sec
This is the rate that the speed setpoint will increase 
from 0 to the SSP1-Slow Roll Speed when the slow 
roll warm-up is initiated.
RRSP4 – Minimum Rated Speed Setpoint
    Screen: Steam System
Range: 100-200 RPM/Sec Default: 200 RPM/Sec
This is the rate that the speed setpoint will increase 
from SSP1-Slow Roll Speed to SSP2-Minimum Rated 
Speed when the ramp-to-rated speed is initiated. 
RRSP5 – Rated Speed Setpoint
    Screen: Steam System
Range: 1-200 RPM/Sec Default: 10 RPM/Sec
This is the rate that the speed setpoint will increase 
from 0 to the SSP1-Slow Roll Speed when the slow 
roll warm-up is initiated.