SECTION 3 - PRINTERS
YORK Update
ChilleR id 0
(c) 1997 - 2004 YORK INTERNATIONAL CORPORATION
Tue 20 Apr 2004 4:46:25 PM
SYSTEM READY TO START
CONTROL PANEL - POWER FAILURE
Controls C.E09.12.00.000.00.551
Run Time 0 Days 0 Hr 0 Min
Operating Hours = 65 Hr
Number Of Starts = 5
Control Source = Local
Evaporator
-------------------------------------------------------
Leaving Chilled Active Setpoint = 42.1 ~F
Chilled Liquid Pump Start Contact = Open
Chilled Liquid Flow Switch = Open
Leaving Chilled Liquid Temperature = 42.0 ~F
Return Chilled Liquid Temperature = 58.0 ~F
Evaporator Pressure = 34.5 Psig
Evaporator Saturation Temperature = 39.4 ~F
Evaporator Refrigerant Temperature = 40.0 ~F
Small Temperature Difference = 2.0 ~F
Condenser
-------------------------------------------------------
Condenser Liquid Pump Start Contact = Open
Condenser Liquid Flow Switch = Open
Leaving Condenser Liquid Temperature = 94.3 ~F
Return Condenser Liquid Temperature = 85.0 ~F
Condenser Pressure = 116.3 Psig
Condenser Saturation Temperature = 96.2 ~F
Small Temperature Difference = 1.9 ~F
Drop Leg Refrigerant Temperature = 90.0 ~F
Sub Cooling Temperature = 6.2 ~F
Compressor
------------------------------------------------------
Discharge Temperature = 120.0 ~F
Oil Sump
-------------------------------------------------------
Oil Pump Run Output = Off
Sump Oil Pressure (LOP) = 33.1 Psig
Pump Oil Pressure (HOP) = 32.9 Psig
Oil Pressure = 0.0 Psid
Oil Sump Temperature = 136.4 ~F
Oil Heater Output = On
Oil Return Solenoid = Off
Variable Speed Oil Pump
-------------------------------------------------------
Oil Pump Drive Command Frequency = 25.0 Hz
Variable Speed Oil Pump Control Mode = Auto
FIGURE 55 - SAMPLE PRINTOUT (STATUS)
Proximity Probe
--------------------------------------------------------
High Speed Thrust Bearing Proximity Different = 2 Mils
Subcooler Level
-------------------------------------------------------
Subcooler Level Setpoint = 0 %
Subcooler Level Pulldown Time Remaining = 0 Sec
Subcooler Level = 50 %
Control Output Signal = 100 %
Subcooler Level Auto/Manual Mode = Auto
Hot Gas Bypass
-------------------------------------------------------
Hot Gas Ratio Calculation = 100 %
Temp Setpoint = 40.9 ~F
Hot Gas Temp Calculation = 0 %
HGV Ramp = 100 %
Control Output Signal = 100 %
HGV Auto/Manual Mode = Auto
Pre-Rotation Vanes
--------------------------------------------------------
PRV Position = 0 %
PRV Ramp = 0 %
PRV Command = 0 %
PRV Motor Switch = Open
PRV Auto/Manual Mode = Auto
Speed Control
--------------------------------------------------------
Speed Setpoint = 0 RPM
MSSP7 - Speed Control Mode = Variable Speed
Turbine Speed = 0 RPM
Control Output Signal = 0.0 %
Turbine Rotation = Open
Speed Setpoint Auto/Manual Mode = Auto
Capacity Control
--------------------------------------------------------
Capacity Ratchet Mode = Hot Gas
Capacity Ratchet: HGV Drive = 100 %
Capacity Ratchet: PRV Drive = 7 %
Capacity Ratchet: SPD Drive = 71.1 %
Anti-Surge Calculated Min. Speed = 3200 RPM
Anti-Surge Calculated Min. PRV = 7 %
Temperature Controller: Selected Override = None
Override Limit = 100.0 %
Temperature Controller: Control Percentage = 0.0 %
Temperature Controller: Control Mode = Inactive
Head Pressure = 81.8 Psid
PD1 - Maximum Pressure Differential = 70.0 Psid
PD2 - Minimum Pressure Differential = 45.0 Psid
MVP1 - High Head Minimum PRV = 5 %
MVP2 - Low Head Minimum PRV = 0 %
MSP1 - High Head Minimum Speed = 4500 RPM
MSP2 - Low Head Minimum Speed = 3600 RPM