SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION
FORM 160.67-O1 
ISSUE DATE: 4/1/2015
2
CONFIGURATION SCREEN 3
   LD09279
FIGURE 39 - CONFIGURATION SCREEN 3
OVERVIEW
This screen is used to configure one spare analog out-
put and three spare digital outputs to duplicate specific 
existing I/O points. These spares may be used for re-
mote signaling or to replace an existing point in the 
event of a hardware failure. 
PROGRAMMABLE
CAO – Configurable Analog Output 
    Screen: N/A
Range:  Governor Position/Hotwell Level/HGV Position/Turbine      
Speed/Steam Inlet Position
Default: Governor Position
This setpoint determines which existing analog output 
control logic drives the 4-20 mA output signal from the 
Frick Analog I/O Board analog output Channel #2. For 
example, with the default setpoint, this output will be 
4 mA at 0% and 20 mA at 100% control signal to the 
turbine governor valve analog output.
CDOA – Configurable Digital Output 
    Screen: N/A
Range:  Compressor Oil Pump/Turbine Oil Pump/Hotwell Pump/ 
Vacuum Pump/Turbine Start Relay
Default: Compressor Oil Pump
This setpoint determines what existing digital output 
control logic drives the 120 VAC digital output on the 
Frick Digital I/O Board digital output Channel #22. 
For example, with the default setpoint, this output is on 
when the compressor VS oil pump drive is enabled to 
start the compressor oil pump. If the setpoint is Hotwell 
or Vacuum Pump, this output is on if either the lead or 
stand-by pump run output is on. 
CDOB – Configurable Digital Output 
    Screen: N/A
Range:  Compressor Oil Pump/Turbine Oil Pump/Hotwell Pump/ 
Vacuum Pump/Turbine Start Relay
Default: Compressor Oil Pump
This setpoint determines what existing digital output 
control logic drives the 120 VAC digital output on the 
Frick Digital I/O Board digital output Channel #23. For 
example, if set for Turbine Oil Pump, this output is on 
when the turbine auxiliary oil pump run output is on.   
CDOC – Configurable Digital Output 
    Screen: N/A
Range:  Compressor Oil Pump/Turbine Oil Pump/Hotwell Pump/ 
Vacuum Pump/Turbine Start Relay
Default: Compressor Oil Pump
NOTE: OptiView
™
 Control Center Screens shown may NOT represent the exact screens according to the software version utilized.