SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION
If the Steam Flow Transmitter produces an output
which is linear with the differential pressure drop
across a flow sensing element, this must be set to
Square Root. The logic will then extract the square root
of the input signal to provide a display that is linear
with the steam flow.
FSP2 – Evaporator Flow Transmitter Signal
Type
Screen: Evaporator
Range: Linear/Square Root Default: Linear
If the Evaporator Flow Transmitter produces an out-
put which is linear with the differential pressure drop
across a flow sensing element, this must be set to
Square Root. The logic will then extract the square root
of the input signal to provide a display that is linear
with the chilled liquid flow.
FSP2 – Condenser Flow Transmitter Signal
Type
Screen: Condenser
Range: Linear/Square Root Default: Linear
If the Condenser Flow Transmitter produces an out-
put which is linear with the differential pressure drop
across a flow sensing element, this must be set to
Square Root. The logic will then extract the square root
of the input signal to provide a display that is linear
with the cooling liquid flow.
Change Setpoints
Access Level Required: SERVICE
This key enables the field selection cursor. The opera-
tor may then toggle between the programmable data
fields using the Cursor Arrow keys.
NAVIGATION
Page Up
Access Level Required: VIEW
Causes an instant return to Configuration Screen 1.
Page Down
Access Level Required: VIEW
Moves to the Configuration Screen 3.
Home
Access Level Required: VIEW
Causes an instant return to the Home Screen.
Setpoints
Access Level Required: VIEW
Causes an instant return to the Setpoints Screen.
Pressure Setpoints
Access Level Required: VIEW
Moves to a sub-screen that allows programming of
various pressure thresholds pertaining to the operation
of the chiller.
Time Setpoints
Access Level Required: VIEW
Moves to a sub-screen that allows programming of
various time delays pertaining to the operation of the
chiller.
Speed Setpoints
Access Level Required: VIEW
Moves to a sub-screen that allows programming of
various speed thresholds pertaining to the operation of
the chiller.
Ramp Rate Setpoints
Access Level Required: VIEW
Moves to a sub-screen that allows programming of
various speed setpoint and valve control signal ramp
rates pertaining to the operation of the chiller