SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION
FRICK I/O BOARD ANALOG INPUT
ENGLISH RANGE METRIC RANGE
LOW HIGH UNITS LOW HIGH UNITS
Turbine Shaft End Horizontal Vibration (Optional) 
0.0 5.0 Mils  0.0 127.0 Micrometers 
Turbine Shaft End Vertical Vibration (Optional)
0.0 5.0 Mils  0.0 127.0 Micrometers 
Turbine Supply Oil Temperature. 
32.0 302.0 ºF 0.0 150.0 ºC
Turbine Shaft End Brg Temperature (Optional)
32.0 302.0 ºF 32.0 150.0 ºC
Turbine Governor End Horizontal Vibration 
(Optional)
0.0 5.0 Mils  0.0 127.0 Micrometers 
Turbine Governor End Vertical Vibration (Optional)
0.0 5.0 Mils  0.0 127.0 Micrometers 
Turbine Gov. End Brg Temperature (Optional)
32.0 302.0 ºF 32.0 150.0 ºC
Turbine Inlet Steam Temperature 
32.0 842.0 ºF 32.0 450.0 ºC
Compressor Horizontal Vibration (Optional) 
0.0 2.0  In/Sec 0.0 50.8 MM/Sec
Turbine Supply Oil Pressure 
0.0 30.0 PSIG 0.0 206.8 kPaG
Turbine Inlet Steam Pressure 
0.0 300.0 PSIG 0.0 2068.5 kPaG
Compressor Vertical Vibration (Optional) 
0.0 2.0  In/Sec 0.0 50.8 MM/Sec
Chilled Water Flow (Optional) 
0.0 #6000 GPM 0.0 #378.5 L/Sec
PRV Position Feedback Potentiometer
0.0 100.0 % 0.0 100.0 %
Condenser Water Flow (Optional) 
0.0 #8000 GPM 0.0 #504.7 L/Sec
Steam Flow  (Optional) 
0.0 #22000 LB/HR 0.0 #9979.2 Kg/Hr
Turbine First Stage Steam Pressure
0.0 **100.0 PSIG 0.0 **689.5 kPaG
Turbine Exhaust Steam Pressure 
0.0 45.0 PSIA 0.0 310.3 kPaA
Turbine Speed Sensor #1
0.0 5000.0 RPM 0.0 5000.0 RPM
Turbine Speed Sensor #2
0.0 5000.0 RPM 0.0 5000.0 RPM
Hotwell Condensate Level
0.0 100.0 % 0.0 100.0 %
Surface Condenser Outlet Temperature
30 150.0 ºF -1.11 65.6 ºC
#Value shown is example only. Full scale range is programmable on Conguration Screen 2. 
**For NON-Condensing Turbines, The high end of the range of the rst stage steam pressure is 150 PSIG/ 1034.2 KPaG   
ANALOG INPUT RANGES - FRICK I/O BOARD