JOHNSON CONTROLS
152
FORM 160.67-O1 
ISSUE DATE: 4/1/2015
SECTION 3 - PRINTERS
If equipped with HIGH SPEED serial board:
SW1 - off (-) Low when busy
      2 - off 1200 Baud*
      3 - off 1200 Baud*
      4 - on 1200 Baud*
      5 - Not Used
      6 - off no parity
      7 - off  Pin 20 & pin 11 act as busy line
• WEIGH-TRONIX Printer
- IMP-24 Model 2600
SW1 - off 1200 Baud*
      2 - on 1200 Baud*
Model 1220
- Configure Menu
Baud= 1200
Data Bits = 8
Stop Bits = 1
Hshake = Busy-Line
Cols = 32
Invert = No
Font = 5 x 8
Mag = None
- Custom Menu
Auto Seq = No
Zero = 0
Pound sign = #
_(Underscore)
Busy invert = no
Online/offline = yes
Ext Ch Set = no
Print ready = yes
Set Clock = Not Used
Reset Seq = Not Used
•  SEIKO
DipSW1-1 = off Input-Serial
    1-2 = on Printing speed high
    1-3 = on Auto loading - on
    1-4 = off Auto LF - off
    1-5 = on Setting Command - Enable
    1-6 = off Printing density - 100%
    1-7 = on Printing density - 100%
    1-8 = on Printing, density - 100%
DipSW 2-1 = on Printing Columns - 40
      2-2 = on User Font Back-up - on
      2-3 = on Character Select - normal
      2-4 = off Zero - slash
      2-5 = on International character set - American
      2-6 = on International character set - American
       2-7 = on International character set - American
      2-8 = off International character set - American
DipSW 3-1 = on Data length - 8 bits
      3-2 = on Parity Setting - no
      3-3 = on Parity condition - odd
      3-4 = on Busy control - H/W busy
      3-5 = on Baud rate select - 1200*
      3-6 = off Baud rate select - 1200*
      3-7 = on Baud rate select - 1200*
      3-8 = off Baud rate select - 1200*
* Settings shown for 1200 Baud. Other Baud rates can 
be selected. Refer to Printer manufacturer’s manual 
supplied with Printer.
CONTROL CENTER SETUP
Chiller ID
Access Level Required: OPERATOR
Using the COMMS Screen, assign an Identification 
number to the chiller. This number will appear at the 
top of each report.