4 Johnson Controls Unitary Products
246750-YTG-M-0908
COOLING CAPACITY - With Air Handler Coils
UNIT MODEL
AIR HANDLER
COIL
1
MODEL
COOLING
MODEL W STAGE
RATED
CFM
NET
MBH
SENSIBLE SEER EER
YZE02411
AV24 17
1 535 18.6 13.6
15.00
13.00
2 800 24.0 18.6 12.50
AV36 17
1 535 18.6 13.6
15.00
13.00
2 800 24.0 18.6 12.50
MV12B 17 FC/MC30B
1 620 18.6 13.6
14.25
12.00
2 800 24.0 18.6 11.50
MV12B 17 FC/MC35B
1 650 18.1 14.4
15.00
12.15
2 775 24.0 19.6 12.00
MV16C 21 FC/MC35C
1 650 18.6 13.6
15.00
13.00
2 775 24.0 18.6 12.50
MV12B 17 FC/MC36B
1 620 18.6 13.6
15.00
11.50
2 800 24.6 18.6 12.00
MV12B 17 FC/MC42B
1 650 18.1 14.4
15.00
12.15
2 775 23.6 19.6 12.00
MV16C 21 FC/MC42C
1 650 18.6 13.6
15.00
13.00
2 775 24.0 18.6 12.50
YZE03611
AV36 17
1 830 25.0 17.5
15.75
12.70
2 1200 35.4 24.2 12.00
AV48 24
1 830 25.0 17.5
15.75
12.70
2 1200 35.4 24.2 12.00
MV12B 17 FC/MC35B
1 775 24.4 17.2
14.75
12.55
2 1200 34.0 23.9 11.50
MV12B 17 FC/MC42B
1 775 24.4 17.2
14.75
12.55
2 1200 34.0 23.9 11.50
MV16C 21 FC/MC48C
1 775 25.0 17.5
15.00
12.85
2 1200 35.4 24.2 12.00
MV12D 24 FC/MC48D
1 775 24.8 17.5
15.75
12.70
2 1200 35.4 24.2 12.00
YZE04811
AV48 24
1 1135 33.2 23.5
15.00
13.30
2 1600 45.0 32.8 12.50
AV/SV*60 24
1 1135 33.2 23.5
15.00
13.30
2 1600 45.0 32.8 12.50
F*FV060 24
1 1000 33.2 23.5
15.50
13.10
2 1600 46.0 32.8 12.15
MV20D 24 FC/MC60D
1 1000 33.2 23.5
15.50
13.05
2 1600 46.0 34.4 12.00
MV20D 24 FC/MC62D
1 1000
33.4 23.7
15.50
13.20
2 1600 47.0 34.7 12.00
YZE06011
AV60 24
1 1145 38.5 27.0
13.50
11.55
2 1800 53.5 38.5 10.25
F*FV060 24
1 1200 38.0 27.0
13.75
11.55
2 1900 53.0 38.5 10.20
MV20D 24 FC/MC60D
1 1200 38.0 27.0
13.75
11.50
2 1900 53.0 38.5 11.00
MV20D 24 FC/MC62D
1 1175 38.0 26.9
14.00
11.65
2 1800 54.0 38.9 10.40
Rated in accordance with DOE test procedures (Federal Register 12-27-79 and 3-18-88) and ARI Standards 210.
Cooling MBH based on 80°F entering air temperature, 50% RH, and rated air flow.
EER (Energy Efficiency Ratio) is the total cooling output in BTU’s at 95°F outdoor ambient divided by the total electric power in watt-hours at those conditions.
SEER (Seasonal Energy Efficiency Ratio) is the total cooling output in BTU’s during a normal annual usage period for cooling divided by the total electric power
input in watt-hours during the same period.
1. G2FD coils available with a factory installed horizontal drain pan. See price pages for specific model number.