835966-UIM-E-0814
OUTDOOR SPLIT-SYSTEM HEAT PUMP
MODELS:
16 SEER - YZF, HC6B, HL6B SERIES
18 SEER - YZH, HC8B, HL8B SERIES
2 TO 5 TONS
INSTALLATION MANUAL
®
LIST OF SECTIONS
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
UNIT INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
INDOOR EXPANSION DEVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
EVACUATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
SYSTEM CHARGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
ELECTRICAL CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
SYSTEM START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
SYSTEM OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
INSTRUCTING THE OWNER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
START UP SHEET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
LIST OF FIGURES
Typical Installation with Required Clearances . . . . . . . . . . . . . . . . . . . . . . 2
Tubing Hanger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Underground Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Heat Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Typical Field Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Communications Harness Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Communicating HP with Communicating Air Handler or Furnace . . . . . . . 8
Communicating HP with Non-Communicating Air Handler
or Furnace using Communicating Interface Control . . . . . . . . . . . . . . . . . . 8
Multi-wire Terminal Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Thermostat Wiring – Single Stage Heat Pump
(with YGVI control) – Modulating Furnace . . . . . . . . . . . . . . . . . . . . . . . . 10
Thermostat Wiring – Single Stage Heat Pump
(with YGVI control) – Single Stage Furnace (X-13) . . . . . . . . . . . . . . . . . 11
Thermostat Wiring – Single Stage Heat Pump
(with YGVI control) – V/S Air Handler . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Thermostat Wiring – Single Stage Heat Pump
(with YGVI control) – PSC Air Handler . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Thermostat Wiring – Single Stage Heat Pump
(with YGVI control) – V/S Air Handler . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Thermostat Wiring – Two-Stage Heat Pump -
Two-Stage Variable Speed Furnace . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Thermostat Wiring – Two-Stage Heat Pump -
Two-Stage Variable Speed Furnace . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Thermostat Wiring – Two-Stage Heat Pump -
Variable Speed Air Handler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Thermostat Wiring – Two-Stage Heat Pump -
Variable Speed Air Handler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Thermostat Wiring – Two-Stage Heat Pump -
Variable Speed Modulating Furnace . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Thermostat Wiring – Two-Stage Heat Pump -
Variable Speed Modulating Furnace . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Heat Pump Flow Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Wiring Diagram - Single Stage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Wiring Diagram - 2 Stage with PSC Outdoor Fan Motor . . . . . . . . . . . . . 24
Wiring Diagram - 2 Stage with ECM Outdoor Fan Motor . . . . . . . . . . . . . 25
LIST OF TABLES
Maximum / Minimum Operating
Limit
Conditions . . . . . . . . . . . . . . . . .2 R-410A Saturation Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Defrost Initiate Curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
SECTION I: GENERAL
The outdoor units are designed to be connected to a matching indoor
coil with sweat connect lines. Sweat connect units are factory charged
with refrigerant for the smallest rated indoor coil plus 15 feet of field
supplied lines.
Matching indoor coils require a thermostatic expansion valve. The
refrigerant charge may need to be changed for some indoor-outdoor
unit combinations, elevation differences, or total line lengths. Refer to
Application Data covering “General Piping Recommendations and
Refrigerant Line Length” (Part Number 247077).
SECTION II: SAFETY
This is a safety alert symbol. When you see this symbol on
labels or in manuals, be alert to the potential for personal
injury.
Understand and pay particular attention to the signal words DANGER,
WARNING, or CAUTION.
DANGER indicates an imminently hazardous situation, which, if not
avoided, will result in death or serious injury
.
WARNING indicates a potentially hazardous situation, which, if not
avoided, could result in death or serious injury
.
CAUTION indicates a potentially hazardous situation, which, if not
avoided may result in minor or moderate injury
. It is also used to
alert against unsafe practices and hazards involving only property dam-
age.
Improper installation may create a condition where the operation of
the product could cause personal injury or property damage.
Improper installation, adjustment, alteration, service or maintenance
can cause injury or property damage. Refer to this manual for assis-
tance or for additional information, consult a qualified contractor,
installer or service agency.
This product must be installed in strict compliance with the enclosed
installation instructions and any applicable local, state, and national
codes including, but not limited to building, electrical, and mechanical
codes.
R-410A systems operate at higher pressures than R-22 systems. Do
not use R-22 service equipment or components on R-410A equip-
ment. Service equipment
Must Be Rated for R-410A.

Table of Contents

Question and Answer IconNeed help?

Do you have a question about the York YZH and is the answer not in the manual?

York YZH Specifications

General IconGeneral
BrandYork
ModelYZH
CategoryHeat Pump
LanguageEnglish

Summary

SECTION I: GENERAL

LOCATION

Criteria and requirements for selecting the outdoor unit installation location.

ADD-ON REPLACEMENT/RETROFIT

Steps for replacing an R-22 system with an R-410A system.

SECTION III: UNIT INSTALLATION

PIPING CONNECTIONS

Procedures and precautions for connecting refrigerant lines.

SECTION II: SAFETY

GROUND INSTALLATION

Guidelines for installing the unit at ground level.

ROOF INSTALLATION

Requirements for installing units on a roof structure.

WALL MOUNT INSTALLATION

Considerations for mounting units on walls.

UNIT PLACEMENT

General placement guidance for the outdoor unit.

LIQUID LINE FILTER-DRIER

Importance and selection of the liquid line filter-drier.

SECTION IV: INDOOR EXPANSION DEVICE

THERMOSTATIC EXPANSION VALVE TXV INSTALLATIONS

Basic steps and precautions for installing a TXV kit.

SECTION V: EVACUATION

SECTION VI: SYSTEM CHARGE

MEASURE INDOOR AIR FLOW

Procedure to determine and set the correct indoor airflow.

CHARGING THE UNIT

Guidelines and methods for charging the system with refrigerant.

SECTION VII: ELECTRICAL CONNECTIONS

GENERAL INFORMATION & GROUNDING

Requirements for electrical supply, grounding, and wiring.

FIELD CONNECTIONS POWER WIRING

Steps for making power wiring connections to the unit.

FIELD CONNECTIONS CONTROL WIRING CONVENTIONAL

Control wiring connections for conventional systems.

FIELD CONNECTIONS CONTROL WIRING COMMUNICATING

Control wiring connections for communicating systems.

SECTION VIII: SYSTEM START-UP

ENERGIZE CRANKCASE HEATER

Procedure to energize the crankcase heater before operation.

DEFROST OPERATION

Information on defrost curve selection and jumper settings.

SECTION IX: SYSTEM OPERATION

REQUIRED CONTROL SETUP

Steps for proper system operation setup.

SECTION X: INSTRUCTING THE OWNER

MAINTENANCE

Routine maintenance procedures for the unit.

SECTION XI: WIRING DIAGRAM

WIRING DIAGRAM SINGLE STAGE

Schematic for single-stage wiring connections.

WIRING DIAGRAM 2 STAGE WITH PSC OUTDOOR FAN MOTOR

Wiring schematic for 2-stage units with PSC fan.

WIRING DIAGRAM 2 STAGE WITH ECM OUTDOOR FAN MOTOR

Wiring schematic for 2-stage units with ECM fan.

SECTION XII: START UP SHEET