Description
These units are completely assembled, piped and wired at the factory
to provide one-piece shipment and rigging. Each unit is pressurized
with a holding charge of Refrigerant R-410A for storage and/or ship-
ping.
The compact design, clean styling, low silhouette, and quiet operation
make these condensing units suitable for almost any outdoor location.
On rooftops . . . because they weigh much less than a single package
unit of similar capacity and are much easier to rig and support. At
ground level . . . because their ample sub-cooling capacity allows them
to be located three or more stories below the evaporator coil.
Every condenser coil is pressurized with air to 325 psig and leak
tested. After assembly, the unit is pressurized with a combination of
Refrigerant R-410A and nitrogen to 450 psig for pressure testing and
additional leak testing. During this pressure test, the operation of the
high pressure control is checked. As the unit is being evacuated and
dehydrated, the operation of the low pressure control is checked.
Every compressor, condenser fan motor, crankcase heater, and elec-
trical control circuit is checked to assure a trouble-free start-up and
years of reliable operation.
The condenser fan guards are vinyl-coated to provide additional rust
protection and to enhance the appearance of the unit.
Compressors are mounted on rubber isolators to reduce the transmis-
sion of vibration. Vertical discharge condenser fans direct sound
upward and away from any surrounding structures.
All sheet metal parts are constructed of commercial grade galvanized
steel. After fabrication, each part is thoroughly cleaned to remove any
grease or dirt from its surfaces. The external parts are coated with a
powder paint to assure a quality finish for many years. This UL
approved coating system has passed the 750-hour, 20% salt spray
test per ASTM Standard B117.
All models include a 1-year limited warranty on the complete unit. An
additional 4-year extended compressor warranty is available as an
option on all models.
A matching line of Evaporator Blower units is also offered to meet your
precise capacity and air handling requirements.
Question and Answer IconNeed help?

Do you have a question about the York YJ-30 and is the answer not in the manual?

York YJ-30 Specifications

General IconGeneral
BrandYork
ModelYJ-30
CategoryHeat Pump
LanguageEnglish

Summary

Description

Product Nomenclature

Condensing Unit Features and Benefits

Condensing Unit Accessories

Details on optional accessories like low ambient controls, phase monitors, and hot gas bypass kits.

Guide Specifications

Installer Requirements

Specifies installer duties, including adherence to plans, manufacturer recommendations, and local codes.

Unit Compliance and Features

Details unit approvals, assembly, testing, warranty, and documentation availability.

Unit Construction Details

Covers frame, finish, access panels, and coil construction for durability and appearance.

Component Specifications

Outlines requirements for compressors, fan motors, wiring, and refrigerant piping.

Physical Data

Unit Limitations

Applied Voltage and Temperature Limits

Specifies applicable voltage ranges and outdoor/indoor temperature limits for cooling operation.

Cooling Ratings

Presents gross capacity, kW, and EER ratings for condensing units at specific conditions.

Capacity Performance

Sound Performance

Electrical Data

Provides detailed electrical specifications for compressors and fan motors across different voltages.

Typical Wiring Diagrams

Typical Field Wiring Diagrams

Condenser Control Box Connections

Illustrates thermostat connections to the SE control board in the condenser control box.

Evaporator Control Box Wiring

Shows typical field wiring for evaporator units matched with the condenser.

Typical Liquid Line Solenoid Wiring

Weight And Dimensions

Corner Weights and Center of Gravity

Provides corner weights and center of gravity data for rigging and handling.

Unit Dimensions and Clearances

Unit Dimensions

Detailed inch measurements for various points (A through H) of the YJ units.

Piping and Electrical Connections

Describes piping connection locations and routing options, plus electrical connection points.

Unit Clearances

Specifies minimum clearances required around the unit for proper operation and maintenance.