EasyManua.ls Logo

York YZE02411 - Page 47

York YZE02411
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Johnson Controls Unitary Products 47
246750-YTG-M-0908
Multipliers for determining the performance with other indoor section.
NOTE: KW RATING IS FOR OUTDOOR AND INDOOR UNITS.
LOW CFM
Continued on Page 48.
HEATING PERFORMANCE DATA - LOW CFM 1-STAGE OPERATION
OUTDOOR UNIT MODEL NO. YZE02411
INDOOR COIL MODEL NO. FC/MC/PC36B + MV12B
AIR TEMP.
ENTERING
OUTDOOR
UNIT
AIR TEMP.
ENTERING
INDOOR
COIL
ID CFM
550 600 650
MBTUH KW C.O.P. MBTUH KW C.O.P. MBTUH KW C.O.P.
60
60 23.4 1.6 4.3 23.5 1.5 4.5 23.7 1.5 4.8
70 21.7 1.8 3.6 22.1 1.7 3.8 22.5 1.7 4.0
80 20.1 2.0 3.0 20.7 1.9 3.2 21.4 1.9 3.4
47
60 19.5 1.5 3.8 19.5 1.4 4.0 19.6 1.4 4.1
70 18.8 1.7 3.2 18.9 1.7 3.3 19.0 1.6 3.4
80 18.1 2.0 2.7 18.3 1.9 2.8 18.4 1.9 2.9
40
60 16.8 1.4 3.5 16.7 1.3 3.6 16.7 1.3 3.8
70 15.7 1.6 2.9 16.0 1.6 3.0 16.2 1.5 3.2
80 14.6 1.8 2.4 15.2 1.8 2.5 15.8 1.7 2.7
30
60 15.4 1.3 3.4 15.4 1.3 3.5 15.5 1.3 3.6
70 14.4 1.5 2.8 14.4 1.5 2.9 14.5 1.4 3.0
80 13.3 1.6 2.4 13.4 1.6 2.4 13.5 1.6 2.5
17
60 12.3 1.4 2.5 12.3 1.4 2.6 12.4 1.4 2.7
70 10.7 1.6 1.9 10.9 1.6 2.0 11.1 1.6 2.1
80 9.2 1.8 1.5 9.5 1.8 1.5 9.8 1.8 1.6
10
60 10.5 1.4 2.2 10.7 1.4 2.3 10.8 1.3 2.4
70 9.4 1.5 1.8 9.6 1.5 1.9 9.8 1.5 2.0
80 8.3 1.6 1.5 8.5 1.6 1.6 8.8 1.6 1.6
NOTE:
ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Air Handler Coil
MBH KW COP
AV24 – 1.00 1.00 1.00
AV36 – 1.00 1.00 1.00
MV12B FC/MC30B 1.00 1.00 1.00
MV12B FC/MC35B 1.00 1.00 1.00
MV12B FC/MC36B 1.00 1.00 1.00
MV12B FC/MC42B 1.00 1.00 1.00
MV16C FC/MC35C 1.00 1.00 1.00
MV16C FC/MC42C 1.00 1.00 1.00