Johnson Controls Unitary Products 53
246750-YTG-M-0908
Multipliers for determining the performance with other indoor sections.
NOTE: KW RATING IS FOR OUTDOOR AND INDOOR UNITS.
HIGH CFM
Continued on Page 54.
HEATING PERFORMANCE DATA - HIGH CFM 2-STAGE OPERATION
OUTDOOR UNIT MODEL NO. YZE03611
INDOOR COIL MODEL NO. FC/MC/PC48C + MV16C
AIR TEMP.
ENTERING
OUTDOOR
UNIT
AIR TEMP.
ENTERING
INDOOR
COIL
ID CFM
1100 1200 1300
MBTUH KW C.O.P. MBTUH KW C.O.P. MBTUH KW C.O.P.
60
60 37.7 2.6 4.3 38.4 2.5 4.5 39.1 2.4 4.7
70 36.7 2.8 3.8 37.2 2.7 4.0 37.8 2.7 4.1
80 35.7 3.0 3.4 36.0 3.0 3.6 36.5 2.9 3.7
47
60 34.5 2.4 4.2 34.3 2.4 4.3 34.2 2.3 4.3
70 32.9 2.7 3.6 33.0 2.6 3.7 33.2 2.6 3.8
80 31.3 2.9 3.1 31.7 2.9 3.2 32.1 2.8 3.3
40
60 30.4 2.3 3.8 30.7 2.3 3.9 31.0 2.3 4.0
70 29.3 2.6 3.3 29.8 2.5 3.4 30.4 2.5 3.5
80 28.3 2.9 2.9 29.0 2.8 3.0 29.7 2.8 3.1
30
60 25.6 2.2 3.4 24.6 2.1 3.4 23.7 2.0 3.4
70 25.7 2.5 3.0 25.1 2.4 3.0 24.5 2.4 3.0
80 25.9 2.8 2.7 25.6 2.7 2.8 25.3 2.7 2.8
17
60 20.8 2.1 2.9 20.9 2.1 2.9 21.0 2.1 2.9
70 19.9 2.3 2.5 20.8 2.4 2.6 21.8 2.4 2.7
80 18.9 2.6 2.2 20.7 2.6 2.3 22.6 2.7 2.5
10
60 19.3 2.1 2.7 19.7 2.1 2.7 20.1 2.1 2.8
70 17.9 2.4 2.2 19.1 2.4 2.4 20.3 2.4 2.5
80 16.4 2.6 1.9 18.5 2.6 2.1 20.5 2.6 2.3
NOTE:
ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Air Handler Coil
MBH KW COP
AV36 – 1.00 1.00 1.00
AV48 – 1.01 1.00 1.01
MV12B FC/MC35B 1.00 1.00 1.00
MV12B FC/MC42B 1.00 1.00 1.00
MV16C FC/MC48C 1.00 1.00 1.00
MV12D FC/MC48D 1.00 1.00 1.00