Johnson Controls Unitary Products 55
246750-YTG-M-0908
Multipliers for determining the performance with other indoor sections.
NOTE: KW RATING IS FOR OUTDOOR AND INDOOR UNITS.
LOW CFM
Continued on Page 56.
HEATING PERFORMANCE DATA - LOW CFM 1-STAGE OPERATION
OUTDOOR UNIT MODEL NO. YZE04811
INDOOR COIL MODEL NO. FC/MC/PC60D + MV20D
AIR TEMP.
ENTERING
OUTDOOR
UNIT
AIR TEMP.
ENTERING
INDOOR
COIL
ID CFM
950 1000 1050
MBTUH KW C.O.P. MBTUH KW C.O.P. MBTUH KW C.O.P.
60
60 38.9 2.5 4.6 39.3 2.5 4.7 39.8 2.4 4.8
70 37.6 2.8 4.0 37.8 2.7 4.1 38.1 2.7 4.2
80 36.2 3.1 3.4 36.3 3.0 3.6 36.4 2.9 3.7
47
60 33.1 2.4 4.1 33.2 2.3 4.2 33.4 2.3 4.3
70 31.3 2.6 3.5 31.8 2.6 3.6 32.3 2.6 3.7
80 29.6 2.9 3.0 30.4 2.8 3.1 31.2 2.8 3.2
40
60 29.4 2.3 3.7 29.7 2.3 3.8 29.9 2.3 3.9
70 28.4 2.7 3.1 28.7 2.6 3.2 28.9 2.6 3.3
80 27.4 3.0 2.7 27.7 2.9 2.8 28.0 2.9 2.8
30
60 25.6 2.2 3.4 25.5 2.2 3.4 25.5 2.2 3.4
70 24.3 2.6 2.8 24.3 2.6 2.8 24.3 2.6 2.8
80 23.0 2.9 2.3 23.0 2.9 2.3 23.1 2.9 2.3
17
60 19.7 2.3 2.6 19.6 2.2 2.6 19.4 2.2 2.6
70 17.3 2.6 2.0 17.2 2.5 2.0 17.0 2.5 2.0
80 15.0 2.9 1.5 14.8 2.8 1.6 14.6 2.7 1.6
10
60 15.9 2.2 2.1 15.9 2.2 2.1 15.9 2.2 2.1
70 14.9 2.5 1.7 15.0 2.5 1.8 15.0 2.5 1.8
80 13.9 2.8 1.4 14.0 2.8 1.5 14.1 2.7 1.5
NOTE:
ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Air Handler Coil
MBH KW COP
F*FV060 – 1.00 1.01 0.99
AV48 – 1.00 1.01 0.99
AV60 – 1.00 1.00 1.00
MV20D FC/MC60D 1.00 1.01 0.99
MV20D FC/MC62D 1.00 1.01 0.99