EasyManua.ls Logo

York ZE048 - Page 18

York ZE048
81 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5188235-YIM-B-1016
18 Johnson Controls Unitary Products
060
(5.0)
208-1-60 24.4 144.2 38 4.4 6.7 0
NONE - - - 41.6 50
E05 4 1 19.2 41.6 50
E07 5.6 1 26.9 42 60
E10 8 1 38.5 56.5 60
E15 11.9 2 57.2 79.9 80
E20 15.9 2 76.4 103.9 110
E30 22.2 2 106.7 141.8 150
230-1-60 24.4 144.2 38 4.4 6.7 0
NONE - - - 41.6 50
E05 5.3 1 22.1 41.6 50
E07 7.5 1 31.2 47.4 60
E10 10.6 1 44.2 63.6 70
E15 15.9 2 66.2 91.2 100
E20 21.2 2 88.3 118.8 125
E30 29.6 2 123.3 162.5 175
208-3-60 16 110 24.9 4.4 4.3 0
NONE - - - 28.7 35
E05 4 1 11.1 28.7 35
E07 5.6 1 15.5 28.7 35
E10 8 1 22.2 33.1 40
E15 11.9 2 33 46.7 50
E20 15.9 2 44.1 60.5 70
E30 22.2 2 61.6 82.4 90
230-3-60 16 110 24.9 4.4 4.3 0
NONE - - - 28.7 35
E05 5.3 1 12.7 28.7 35
E07 7.5 1 18 28.7 35
E10 10.6 1 25.5 37.2 40
E15 15.9 2 38.2 53.2 60
E20 21.2 2 51 69.1 70
E30 29.6 2 71.2 94.4 100
460-3-60 7.8 52 12.1 4.4 2.1 0
NONE - - - 14.1 20
E07 6.8 1 8.2 14.1 20
E10 10.1 1 12.1 17.8 20
E15 13.6 2 16.4 23.1 25
E20 19.5 2 23.5 31.9 35
E30 28.8 2 34.6 45.9 50
575-3-60 5.7 38.9 8.9 4.4 1.9 0
NONE - - - 10.8 15
E10 10.6 1 10.2 15.1 20
E15 15.9 2 15.3 21.5 25
E20 21.2 2 20.4 27.9 30
E30 30.4 2 29.3 38.9 40
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
ZE036-060 - Without Powered Convenience Outlet (Belt Drive) (Continued)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
Max
Fuse
2
/
Breaker
3
Size
(Amps)
RLA LRA MCC FLA FLA FLA Model kW Stages Amps

Table of Contents

Other manuals for York ZE048

Related product manuals