5188235-YIM-B-1016
28 Johnson Controls Unitary Products
060
(5.0)
208-1-60 24.4 144.2 38 4.4 7.6 10
NONE - - - 52.5 70
E05 4 1 19.2 52.5 70
E07 5.6 1 26.9 55.7 70
E10 8 1 38.5 70.1 80
E15 11.9 2 57.2 93.5 100
E20 15.9 2 76.4 117.6 125
E30 22.2 2 106.7 155.4 175
230-1-60 24.4 144.2 38 4.4 7.6 10
NONE - - - 52.5 70
E05 5.3 1 22.1 52.5 70
E07 7.5 1 31.2 61.1 70
E10 10.6 1 44.2 77.2 80
E15 15.9 2 66.2 104.8 110
E20 21.2 2 88.3 132.4 150
E30 29.6 2 123.3 176.2 200
208-3-60 16 110 24.9 4.4 7.6 10
NONE - - - 42 50
E05 4 1 11.1 42 50
E07 5.6 1 15.5 42 50
E10 8 1 22.2 49.8 50
E15 11.9 2 33 63.3 70
E20 15.9 2 44.1 77.2 80
E30 22.2 2 61.6 99 100
230-3-60 16 110 24.9 4.4 7.6 10
NONE - - - 42 50
E05 5.3 1 12.7 42 50
E07 7.5 1 18 44.6 50
E10 10.6 1 25.5 53.9 60
E15 15.9 2 38.2 69.8 70
E20 21.2 2 51 85.7 90
E30 29.6 2 71.2 111 125