22 Johnson Controls Unitary Products
ZF036-060 Without Powered Convenience Outlet (Direct Drive)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
Max
Fuse
2
/
Breaker
3
Size
(Amps)
RLA LRA MCC FLA FLA FLA Model kW Stages Amps
036
(3.0)
208-1-60 14.7 74.0 23.0 2.3 6.0 0.0
None - - - 26.7 35
E05 4.0 1 19.2 31.5 40
E07 5.6 1 26.9 41.2 45
E10 8.0 1 38.5 55.6 60
E15 11.9 2 57.2 79.0 80
E20 15.9 2 76.4 103.1 110
230-1-60 14.7 74.0 23.0 2.3 6.0 0.0
None - - - 26.7 35
E05 5.3 1 22.1 35.1 40
E07 7.5 1 31.3 46.6 50
E10 10.6 1 44.2 62.7 70
E15 15.9 2 66.3 90.3 100
E20 21.2 2 88.3 117.9 125
208-3-60 9.1 68.0 14.2 2.3 6.0 0.0
None - - - 19.7 25
E05 4.0 1 11.1 21.4 25
E07 5.6 1 15.5 26.9 30
E10 8.0 1 22.2 35.3 40
E15 11.9 2 33.0 48.8 50
E20 15.9 2 44.1 62.7 70
230-3-60 9.1 68.0 14.2 2.3 6.0 0.0
None - - - 19.7 25
E05 5.3 1 12.7 23.4 25
E07 7.5 1 18.0 30.1 35
E10 10.6 1 25.5 39.4 40
E15 15.9 2 38.2 55.3 60
E20 21.2 2 51.0 71.2 80
048
(4.0)
208-1-60 15.7 84.0 24.5 2.3 7.6 0.0
None - - - 29.5 40
E05 4.0 1 19.2 33.5 45
E07 5.6 1 26.9 43.2 45
E10 8.0 1 38.5 57.6 60
E15 11.9 2 57.2 81.0 90
E20 15.9 2 76.4 105.1 110
230-1-60
15.7 84.0 24.5 2.3 7.6 0.0
None - - - 29.5 40
E05 5.3 1 22.1 37.1 45
E07 7.5 1 31.3 48.6 50
E10 10.6 1 44.2 64.7 70
E15 15.9 2 66.3 92.3 100
E20 21.2 2 88.3 119.9 125
208-3-60
11.2 88.0 17.5 2.3 7.6 0.0
None - - - 23.9 30
E05 4.0 1 11.1 23.9 30
E07 5.6 1 15.5 28.9 35
E10 8.0 1 22.2 37.3 40
E15 11.9 2 33.0 50.8 60
E20 15.9 2 44.1 64.7 70
230-3-60
11.2 88.0 17.5 2.3 7.6 0.0
None - - - 23.9 30
E05 5.3 1 12.7 25.4 35
E07 7.5 1 18.0 32.1 35
E10 10.6 1 25.5 41.4 45
E15 15.9 2 38.2 57.3 60
E20 21.2 2 51.0 73.2 80