Loading...
697890-YIM-C-0213
Johnson Controls Unitary Products 23
060
(5.0)
208-1-60
21.1 105.0 33.0 2.3 7.6 0.0
None - - - 36.3 45
E05 4.0 1 19.2 36.3 45
E07 5.6 1 26.9 43.2 50
E10 8.0 1 38.5 57.6 60
E15 11.9 2 57.2 81.0 90
E20 15.9 2 76.4 105.1 110
E30 22.2 2 106.7 142.9 150
230-1-60
21.1 105.0 33.0 2.3 7.6 0.0
None - - - 36.3 45
E05 5.3 1 22.1 37.1 45
E07 7.5 1 31.3 48.6 50
E10 10.6 1 44.2 64.7 70
E15 15.9 2 66.3 92.3 100
E20 21.2 2 88.3 119.9 125
E30 29.6 2 123.3 163.7 175
208-3-60
14.1 88.0 22.0 2.3 7.6 0.0
None - - - 27.5 35
E05 4.0 1 11.1 27.5 35
E07 5.6 1 15.5 28.9 35
E10 8.0 1 22.2 37.3 40
E15 11.9 2 33.0 50.8 60
E20 15.9 2 44.1 64.7 70
E30 22.2 2 61.6 86.5 90
230-3-60 14.1 88.0 22.0 2.3 7.6 0.0
None - - - 27.5 35
E05 5.3 1 12.7 27.5 35
E07 7.5 1 18.0 32.1 40
E10 10.6 1 25.5 41.4 45
E15 15.9 2 38.2 57.3 60
E20 21.2 2 51.0 73.2 80
E30 29.6 2 71.2 98.5 100
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
ZF036-060 Without Powered Convenience Outlet (Direct Drive) (Continued)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
Max
Fuse
2
/
Breaker
3
Size
(Amps)
RLA LRA MCC FLA FLA FLA Model kW Stages Amps

Table of Contents