5168276-XIM-B-0216
Johnson Controls Unitary Products 17
Table 9: Electrical Data
ZF180-240 - Standard Drive
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
1. Minimum Circuit Ampacity.
Max Fuse
2
/
Breaker
3
Size
(Amps)
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
RLA LRA MCC
C1 C2 C1 C2 C1 C2 FLA FLA FLA Model kW Stages Amps
180
(15)
380-3-50 16.7 13 111 101 26 20.3 2.1 6.3 0 NONE - - - 44.4 60
415-3-50 16.7 13 111 101 26 20.3 2.1 6.7 0 NONE - - - 44.8 60
240
(20)
380-3-50 18.6 17.9 118 118 29 28 2.1 8.2 0 NONE - - - 53.6 70
415-3-50 18.6 17.9 118 118 29 28 2.1 9.1 0 NONE - - - 54.5 70