Page. 28
LMV5000.EN202001V6
From oil to gas:
1. Set the main switch on the burner control panel to “OFF”.
2. Close all oil valves in the oil line.
3. Set the selector switch from “OIL” to “GAS”.
4. Switch the load switch to the required setting.
5. Set the flue gas inlet valve of the condenser to standard operation.
6. Open shut off valve A1.
7. Set the main switch on the burner control panel to “ON”.
WARNING:
Before starting the system, check the furnace for oil. If the boiler temperature is
higher than 65 ºC the oil in the furnace may gasify. At the next attempt to start, the
ignition may ignite the gasified oil and may cause an explosion.
Ask the burner engineer to demonstrate the switch from gas to oil and back.