EasyManua.ls Logo

ZEKS Eclipse 250ZPA - 10.0 Troubleshooting

ZEKS Eclipse 250ZPA
31 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ZEKS Eclipse ZPA 90-5000 Desiccant Dryers
www.zeks.com
13
10.0 TROUBLESHOOTING
PROBLEM
Elevated dew point
Blue Moisture Indicater (BMI)
indicates high moisture level.
Excessive pressure drop in
dryer
Failure to shift
Dryer fails to pressurize.
Dryer depressurizes too
rapidly.
Dryer fails to purge.
Excessive back pressure in
regenerating tower (above 5
psig).
Right tower excessively high
pressure at the purge gauge.
PROBABLE CAUSE
Insuf cient purge rate.
Inlet air pressure below design condition.
Flow rate higher than design condition.
Inlet temperature above design condition (120F).
Entrained water entering desiccant bed.
Desiccant contaminated by oil.
Elevated dew point.
BMI wet.
Excessive ow rate.
Inlet pressure below design condition.
No input power.
Defective solenoid valve.
No pilot air.
Pilot-operated diaphragm valve seat failure.
Faulty purge valve.
Purge valve does not close; dryer repressurizing
through inlet valve.
Purge valve does not open. Purge valve stuck in
closed position.
Purge muf er does not pass air.
Purge muf er passes too much air. Air is leaking
across valve.
Improper calibration.
CORRECTIVE ACTION
Check purge ow settings.
Check purge piping for obstruction.
Clean purge piping and muf er.
Check pressure source and system for leakage.
Check ow rate and cause for increased demand.
Correct ow rate condition.
Check aftercooler. Clean and service as necessary.
Check air/moisture separator, pre lter and drains.
Replace dryer desiccant if necessary.
Install suitable pre lter. Replace dryer desiccant.
Refer to “Elevated Dew Point” corrective actions
shown above.
Depending on degree of saturation of the desic-
cant, the BMI may take a week or more of con-
tinuous use to switch back to its blue (dry) state.
Check ow rate and cause for increased air demand.
Check pressure source.
Check power input.
Check solenoid valve.
Check pilot air line. Check that control air line
lter is clean.
Inspect seals and replace as required.
Check that repressurization circuit is sending
control signal.
Check purge valve and its solenoid valve.
Check purge valve and its solenoid valve.
Check purge valve and its solenoid valve. Repair
and replace if necessary.
Check that repressurization circuit is sending
control signal.
Purge muf er is dirty; replace.
Check inlet valve and outlet check valves. Verify
inlet valve is closed to purging tower (0 psig
tower).
Reset when right tower is online.
For troubleshooting procedures, refer to maintenance descriptions in Section 9 as required.

Related product manuals