J
Jody MorrisAug 14, 2025
Why does my ZEKS Eclipse 600ZPA Dryer have an elevated dew point?
- EErin McmillanAug 14, 2025
An elevated dew point in your ZEKS Dryer can stem from several causes. It may be due to an insufficient purge rate, so check the purge flow settings and piping for obstructions, cleaning the piping and muffler if needed. Also, inlet air pressure below the design condition, a flow rate higher than the design condition, or an inlet temperature exceeding 120F can contribute to this issue. Check the pressure source and system for leaks, verify the flow rate, and inspect/service the aftercooler. Finally, entrained water entering the desiccant bed or desiccant contaminated by oil could be the reason. In this case, check the air/moisture separator, prefilter, and drains, replacing the dryer desiccant if necessary. Consider installing a suitable prefilter.