• Even though all the safety systems are in place, before touching any working parts, you must check that
they are not live.
• If any liquid is spilt accidentally on the System, disconnect it and call to ZIGOR support.
• During assembly work, start-up or maintenance, wear goggles to avoid any damage to your eyes due to
accidental electric arcing.
• Use only insulated tools.
• The unit must be protected against rain and excess humidity and installed in a clean atmosphere, without
inflammable liquids, gases or oxidising substances.
• The battery may pose a risk of electric shock or burns due to its high short circuit current.
• If the batteries lose electrolyte or are physically damaged, they must be placed in a container in resistant
to corrosive liquids (acids or alkaline according to the type of battery) and prepared in accordance with
local regulations.
• If the electrolyte comes into contact with the skin, the affected area must be washed immediately with
clean water.
• For the sake of human being safety, please well earth the UPS before starting it.
• Do not throw batteries into a fire as they may explode.
• UPS models with internal batteries can be powered even when the UPS input is not connected to the
mains.
• Do not disconnect the input from the UPS and make sure the UPS is completely off before moving it or
reconfiguring the connection; otherwise, there is a risk of electric shock.
• Only authorized personnel should repair or install the batteries.
• Should you have any problems with the contents of this manual, you must ask ZIGOR for assistance.
Storage precautions
The store where the material is kept must protect the material from the elements, risk of flooding or contact with
water.
The material shall be protected from any risk of overheating due to exposure to direct sunlight or through
windows.
The UPS has lead batteries. The temperature has an influence on auto-discharge and on the service life of the
batteries. Therefore, it is essential to store them in as cool an atmosphere as possible.
The recommended storage temperature is from 15ºC to 25ºC. An increase of 10ºC can reduce the service life of
the battery by 50%. The recommended relative humidity is from 30% to 90%.
To avoid any risk of mechanical shock, do not stack the packages. These must be placed in accordance with the
silkscreen printed details on the boxes used for packaging.
For prolonged periods of storage, voltages must be controlled at the following intervals:
▪ Storage at 20ºC: Every 3 months.
▪ Storage at 30ºC: Every 2 months.
Disconnect the battery if this is to be shut down for a long time.