Disconnect power before servicing the unit to prevent electrical shock.
Monitors liquid levels in pump basins, features Power On LED, alarm LEDs, buzzer, and auxiliary contacts.
Requires 120V, NEMA 4X rating, proper conduit, yearly screw tightening, and 15A breaker.
Drill openings for conduit adapters and install unit using mounting flanges.
Wire line, neutral, ground, float switch, and auxiliary contacts to terminal blocks.
Connect high water float switch to input terminals and use auxiliary contacts for other circuits.
Test by lifting float, silence alarm for 24 hours, reset after condition is remedied.
Secure cord with clamp, ensure unobstructed motion, suspend 7" below desired alarm level.
Install above pump energize level in lift pump or 7" below alarm level in holding tank.
Covers defects for 5 years, excludes misuse, alteration, neglect, or unapproved disassembly.
Disclaims liability for consequential damages and limits implied warranties to duration of express warranty.