MENU - USER LOCK
MENU - SUMMER HEATING
Timed rundown
Thermal rundown
MENU - DOOR CONTACT
Limit level – see Ad1)
Enter PIN 0000~9999
(numeric values only)
Use this menu to set the limits to control the regulator with a
multi-level panel
Use this menu to set heating limits in summer months
Use this menu to set the behaviour of the regulator according to the
door contact
If the outside temperature sensor is not set,
the summer heating mode will operate only according to
the selected time and the temperature will not be taken into
account
Options:
None – Limit inactive
On/O – Only On/O and access to the information menu are
enabled in the main screen
On/O, Temp, Flow – On/O, the information menu, and temperature and air ow
settings can be accessed without password.
Full – Only the information menu can be accessed without password
User mode – Special user mode, see image below
End of winter period
(month number)
Mode:
Fixed
Selearning
(adapts automatically to the
situation (frequency the doors
are opened in a given period)
Start of winter
period (month number)
Enable/disable
function
Enable/disable
function
Temperature limit – the
heating is disabled if
the temperature on the
“Outdoor” sensor is higher
than the one set here
Fixed mode settings
Ventilation rate with
open doors
(20%-100%)
Heating settings with
open doors
Manual = 0%, 50%, 100%
Auto = 15°C-45°C
Timed rundown at minimum
speed: 5s ~ 300s
Timed rundown at maximum
speed: 5s ~ 300s
After the rundown, the unit goes into closed door mode. When unit is o
in closed door mode, if it has electric reheating, the electric exchanger is
cooled. If the doors are opened again, the rundown is interrupted.
After the reaching the temperature, the unit goes into closed door
mode.
When unit is o in closed door mode, if it has electric reheating, the
electric exchanger is cooled.
If the doors are opened again, the rundown is interrupted.
Temperature required for thermal
rundown
OUTLET: 15°C-45°C
INLET: 15°C-30°C
ROOM: 15°C-30°C
THERMOSTAT: N/A
ROOM BMS: 15°C-30°C
Sensor on which the temperature
to be reached will be measured
Options:
Outlet
Inlet
,
Room
Thermostat
Room BMS
– Sensor from the
BMS system
Detailed settings
of the rundown
function
Rundown function:
Disable
Time interval
Temperature (when
reaching a temperature on
the thermostat)
4. CONTROL