Function name Signal type Signal name Description
QCCBAY.1.REM Remote operation allowed
Disconnector (DAXSWI) Binary inputs DAXSWI.1.OP_BLKD Indication that the function is
blocked for open commands
DAXSWI.1.CL_BLKD Indication that the function is
blocked for close commands
DAXSWI.1.UPD_BLKD The update of position
indication is blocked
DAXSWI.1.POSITION Apparatus position indication
DAXSWI.1.OPENPOS Apparatus open position
DAXSWI.1.CLOSEPOS Apparatus closed position
Counters DAXSWI.1.CNT_VAL The value of the operation
counter
Circuit breaker / disconnector
control (GNRLCSWI)
Analog inputs GNRLCSWI.1.L_CAUSE Latest value of the error
indication during command
Binary inputs GNRLCSWI.1.CMD_BLKD Commands are blocked
Binary outputs GNRLCSWI.1.CLOSE_CMD Close command parameter for
DNP3 protocol
GNRLCSWI.1.OPEN_CMD Open command parameter for
DNP3 protocol
Double bit indications GNRLCSWI.1.POSITION Position indication
Interlocking (interface) (SCILO) Binary inputs SCILO.1.EN_CLOSE Close operation at open or
intermediate or bad position is
enabled
SCILO.1.EN_OPEN Open operation at closed or
intermediate or bad position is
enabled
Trip circuit supervision
(TCSSCBR)
Binary inputs TCSSCBR.1.ALARM Trip circuit fault indication
Tripping logic (TRPPTRC) Binary inputs TRPPTRC.1.CL_LKOUT Circuit breaker lockout output
(set until reset)
TRPPTRC.1.TRIP General trip output signal
Fusefailure supervision
(SEQRFUF)
Binary inputs SEQRFUF.1.FUSEF_3PH Three-phase start of function
SEQRFUF.1.FUSEF_U General start of function
SEQRFUF.1.FUSEF_Z Start of current and voltage
controlled function
Circuit breaker condition
monitoring (SSCBR)
Binary inputs SSCBR.1.CB_LIFE_ALM Remaining life of CB reduced to
Life alarm level
SSCBR.1.CLOSEPOS CB is in closed position
SSCBR.1.INVALIDPOS CB is in invalid position (not
positively open or closed)
SSCBR.1.IPOW_ALM Accumulated currents power
(Iyt),exceeded alarm limit
SSCBR.1.IPOW_LO Accumulated currents power
(Iyt),exceeded lockout limit
SSCBR.1.MON_ALM CB 'not operated for long time'
alarm
Table continues on next page
1MRS756791 A Section 2
DNP3 data mappings
630 series 35
Point List Manual