EasyManua.ls Logo

ABB ACH550-UH - Page 185

ABB ACH550-UH
642 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ACH550-UH User’s Manual 1-181
Parameters
8121 REG BYPASS CTRL 0, 1 1 0 (NO)
Selects Regulator by-pass control. When enabled, Regulator by-pass control provides a simple control mechanism
without a PID regulator.
Use Regulator by-pass control only in special
applications.
0 =
NO – Disables Regulator by-pass control. The drive
uses the normal PFA reference: 1106
REF2 SELECT.
1 =
YES – Enables Regulator by-pass control.
The process PID regulator is bypassed.
Actual value of PID is used as the PFA reference
(input). Normally
EXT REF2 is used as the PFA
reference.
The drive uses the feedback signal defined by
4014
FBK SEL (or 4114) for the PFA frequency
reference.
The figure shows the relation between the control
signal 4014
FBK SEL (OR 4114) and the speed
regulated motor’s frequency in a three-motor
system.
Example: In the diagram below, the pumping station’s
outlet flow is controlled by the measured inlet flow (A).
8122 PFA START DELAY 0.00…10.00 s 0.01 s 0.50 s
Sets the start delay for speed regulated motors in the system. Using the delay, the drive works as follows:
Switches on the contactor of the speed regulated motor – connecting the motor to the ACH550 power output.
Delays motor start for the time 8122 PFA START DELAY.
Starts the speed regulated motor.
Starts auxiliary motors. See parameter 8115 for delay.
WARNING! Motors equipped with star-delta starters require a PFA Start Delay.
After the ACH550 relay output switches a motor on, the star-delta starter must switch to the star-connection and
then back to the delta-connection before the drive applies power.
So, the PFA Start Delay must be longer than the time setting of the star-delta starter.
Group 81: PFA Control
Code Description Range Resolution Default S
P 4014
P 8110
P 8109
P 8113
P 8112
A = No auxiliary motors running
B = One auxiliary motor running
C = Two auxiliary motors running
A
B
C
(%)
f
OUT
f
MIN
f
MAX
M
3~
M
3~
M
3~
Outlet pipe3
Outlet pipe2
Outlet pipe1
P1
P2
P3
Sewage
tank
Contactors
P1
P2
P3
Mains 3~
3
3
3
3
ACH550
3
3
Inlet pipe
A

Table of Contents