16 ACS 300 User’s Manual
Chapter 3 - Power Connections
Figure 3-2 Power cable connections.
All mains connections shall be rated 60°C for use in ambient
temperatures up to 45°C. Or 75°C for use in ambient
temperatures up to 50°C. All mains connections shall be
tightened to a torque of 1 Nm.
BRAKE
RES
U2 V2 W2 L1 L2 L3
X2 X1
BRAKE RES U2 V2 W2LN
X2X1
BRAKE RES U2 V2 W2 L1 L2 L3
X2 X1
N
X2
X1
L1 L2 L3PE PE U2 V2 W2PE PE
+ -
A
CS 311-1P1-1 and 1P6-1
A
CS 3_1-2P1-1 to 4P1-1
A
CS 3_1-1P6-3 to 6P6-3
A
CS 3_1-8P7-3
to 016-3
Motor only !
Motor only !
Motor only !
Mains
Mains
Mains
Mains Motor only !
Braking
chopper
Braking
resistor
Braking
resistor
Braking
resistor