ACS 300 User’s Manual 35
Chapter 4 - Control Connections
Figure 4-6 Motor Potentiometer switch S1 selection.
Motor
Potentiometer 2
Switch S1 is in the same position as in Motor potentiometer
selection. Parameter PARAM SET has value 2.
Table 4-15 Motor Potentiometer 2 selection.
The ACS 300 accelerates/decelerates using Page 1/ Page 4
parameters ACC 1/ DEC 1 when changing rotation direction.
Acceleration from 0 Hz to MIN FREQ is also done with ramp 1.
Digital input Function Notes
DI1 Start Connect +24 V DC to Start
DI2 Reverse Connect +24 V DC to reverse
DI3 Increment fr. Connect +24 V DC to increment fr. (ramp 2)
DI4 Decrement fr. Connect +24 V DC to decrement fr. (ramp 2)
DI5 Parameter set selection 0 V= set 1 and +24 V= set 2
OFF ON
0
1
Motor potentiometer